* 1. 0 or 1 for flux vector control.
* 2. The factory setting depends on the capacity of the Inverter.
* 3. The upper limit of the setting range depends on the upper limit set in E1-04.
* 4. When C6-01 = 1, the upper limit is 400.00.
* 5. When using flux vector control, 0 to 2.

Settings for the Control Methods

Autotuning methods depend on the control method set for the Inverter. Make the settings required by the con-
trol method.
Overview of Settings
Make the required settings in quick programming mode and autotuning mode according to the following flow-
chart.
START
NO
Vector control (A1-02 = 2 or 3 )
V/f control?
A1-02=0 or 1)
YES
PG?
NO
(Default:
A1-02=0)
Set E1-03, E2-04, and F1-01.
Set E1-03.
V/f default: 200V/60Hz(400V/60Hz)
V/f default: 200V/60Hz(400V/60Hz)
Motor cable over
50 m or heavy load possibly
causing motor to stall
or overload?
NO
Stationary autotuning for
line-to-line resistance only
END
Note If the motor cable changes to 50 m or longer for the actual installation, perform stationary autotuning for the line-to-line resistance only on-site.
* 1. Use rotational autotuning to increase autotuning accuracy whenever it is okay for the motor to be operated.
* 2. If there is a reduction gear between the motor and PG, set the reduction ratio in F1-12 and F1-13.
* 3. If the maximum output frequency is different from the base frequency, set the maximum output frequency (E1-04) to the value of the base frequency
after autotuning.
YES
A1-02=1
*2
OK to operate
motor during
YES
autotuning?
Rotational
autotuning
Fig 4.3 Settings According to the Control Method
Control mode selection
Load is
NO
connected to motor when
operating motor first time
*1
after autotuning?
YES
Stationary
*3
autotuning 1
Trial Operation Procedures
YES
Stationary
*3
*3
autotuning 2