Omron SYSDRIVE RV Series User Manual page 226

High-function general-purpose inverters
Table of Contents

Advertisement

Deceleration to Stop
If the Stop Command is input (i.e., the Run Command is turned OFF) when b1-03 is set to 0, the motor decel-
erates to a stop according to the deceleration time that has been set. (Factory setting: C1-02 (Deceleration
Time 1))
If the output frequency when decelerating to a stop falls below b2-01, the DC injection brake will be applied
using the DC current set in b2-02 only for the time set in b2-04.
For deceleration time settings, refer to page 6-23 Setting Acceleration and Deceleration Times.
The operation after starting or stopping depends on the setting of b1-05 when flux vector control is selected
(A1-02 = 3).
Run Command OFF
Frequency reference
via analog input
0
(frequency reference)
b1-05=1
(Coast)
b1-05=2
(Run on E1-09)
b1-05=3
(Zero-speed)
-18
6
Run Command
Output frequency
Decelerates to stop at
deceleration time
Fig 6.15 Deceleration to Stop
b1-05=0
Injection brake
time at start
b2-03
Baseblock
Injection brake
time at start
Baseblock
b2-03
Injection brake
time at start
Baseblock
b2-03
Injection brake
time at start
Baseblock
b2-03
Fig 6.16 Deceleration to Stop (for Flux Vector Control)
ON
OFF
DC injection brake
DC injection brake time
when stopping (b2-04)
ON
Zero-speed
control
b2-04
OFF
E1-09
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Zero-speed
control
Baseblock
b2-04
Frequency reference drops to less
than E1-09 and zero-speed control
starts when motor speed drops to
b2-01.
Baseblock
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Zero speed control
Baseblock
b2-04
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Zero-speed control
Baseblock
b2-04