Options; Performing Speed Control With Pg - Omron SYSDRIVE RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

Options

This section explains the Inverter option functions.

Performing Speed Control with PG

This section explains functions with V/f control with PG and flux vector control.
Related Parameters
Param-
eter
Number
PG parame-
ter
F1-01
PG Pulses/
Rev
Operation
selection at
PG open
circuit
(PGO)
F1-02
PG Fdbk
Loss Sel
Operation
selection at
overspeed
(OS)
F1-03
PG Over-
speed Sel
-192
6
Name
Description
Display
Sets the number of PG (pulse
generator or encoder) pulses.
Sets the number of pulses
per motor revolution.
Sets the PG disconnection
stopping method.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency
stop using the
deceleration time in C1-
09.)
3: Continue operation (To
protect the motor or
machinery, do not
normally make this
setting.)
Sets the stopping method
when an overspeed (OS)
fault occurs.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency
stop using the
deceleration time in C1-
09.)
3: Continue operation (To
protect the motor or
machinery, do not
normally make this
setting.)
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to
600
No
No
60000
0 to 3
1
No
No
0 to 3
1
No
No
Regis-
V/f
Open
Flux
ter
with
Loop
Vec-
PG
Vector
tor
Q
No
Q
380H
A
No
A
381H
A
No
A
382H

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

3g3rv-v1

Table of Contents