400 V Class Inverters of 185 kW and 220 kW
Removing the Cooling Fan
1. Remove the terminal cover and top and bottom front covers from the front of the Inverter.
2. Remove any cables that are connected to the cooling fan power relay board.
3. Remove the fan cover screws and pull out the fan covers from the Inverter.
4. Remove the cooling fan from the fan cover and replace it with a new one.
Mounting the Cooling Fan
After attaching a new cooling fan, reverse the above procedure to attach all of the components.
When attaching the cooling fan to the mounting bracket, be sure that the airflow faces the top of the Inverter.
Make sure that the fan cable and the fan ground cable are not tangled or pinched.
Front cover mounting screws
Top front
cover
Bottom
front
cover
Terminal cover mounting screws
Fan cover mounting screws
Enlarged view
Fan cover mounting screws
Fig 8.11 Cooling Fan Replacement (400 V Class Inverters of 185 kW and 220 kW)
Fan cover
Terminal
cover
Cooling fan mounting screws
Maintenance and Inspection
Fan power relay
board
Fan cover
Fan cable
Fan ground
cable
Fan airflow
direction
Colling fan
Finger guard