SNMP Settings Display

l SNMP
Setting
SNMP service
*2
Port No.
Address
Location
Send a recognition
trap
*1.
If you select the Use Option for the SNMP service, you also have to set Recognition 1 and 2 as descri-
bed below.
*2.
The following ports are used by the system and cannot be set by the user: 25, 53, 68, 110, 2222, 2223,
2224, 9600, and 44818.
Additional Information
Refer to Section 11 SNMP Agent on page 11-1 for details on the SNMP service.
NX-series EtherNet/IP Unit User's Manual (W627)
7 Sysmac Studio Settings for the EtherNet/IP Port
Description
Specify whether to use the SNMP monitor service.
If the Do not use Option is selected, an SNMP manager cannot
connect from an external device.
Set the port number to use to connect to the SNMP server that is
used to connect from an SNMP manager.
This setting does not normally need to be changed.
Set the communications device administrator's name and instal-
lation location as text information. You do not necessarily have to
input all items. This information is read by the SNMP manager.
(You can input up to 255 single-byte alphanumeric characters for
each item.)
Set whether to send an authentication trap.
If you select Send a recognition trap and there is access from
an SNMP manager that is not set in Recognition 1 or Recognition
2, an authentication trap is sent to the SNMP manager.
If you select Send a recognition trap, specify the SNMP trap
settings on the SNMP Trap Tab.
Default
Do not use
*1
161
None
None
Not selected
7-11