6 Device Variables Related to the NX-series EtherNet/IP Unit
Variable name
EIP_Comm2Status.TagAdrErr
Meaning
CIP Communications2 Tag Name Resolution
Error
Function
Indicates that the tag resolution for CIP communications 2 failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
The size of the network variable is different from the tag settings.
The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the NX-series EtherNet/IP Unit.
There is no network variable in the NX-series EtherNet/IP Unit that corresponds to the tag setting.
FALSE: Other than the above.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
l Functional Classification: NX-series EtherNet/IP Unit Status
Variable name
ETN_Port1Status.EtnOnlineSta
Meaning
Port1 Online
Function
Indicates that the EtherNet/IP port's communications can be used via the communications port 1 (that is, the link
is ON, IP address is defined, and there are no errors.)
TRUE: The EtherNet/IP port's communications can be used.
FALSE: The EtherNet/IP port's communications is disabled due to an error in initial processing, restart process-
ing, or link OFF status.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
Variable name
ETN_Port2Status.EtnOnlineSta
Meaning
Port2 Online
Function
Indicates that the EtherNet/IP port's communications can be used via the communications port 2 (that is, the link
is ON, IP address is defined, and there are no errors.)
TRUE: The EtherNet/IP port's communications can be used.
FALSE: The EtherNet/IP port's communications is disabled due to an error in initial processing, restart process-
ing, or link OFF status.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
Variable name
EIP_Comm1Status.TDLinkRunSta
Meaning
CIP Communications1 Tag Data Link Communi-
cations Status
Function
Indicates that at least one connection is in normal operation in CIP communications 1.
TRUE: Normal operation
FALSE: Other than the above.
Data type
BOOL
R/W access
R
Usage in user pro-
Possible.
gram
6-24
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Retained
Not retained.
Related in-
---
structions
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Do not publish.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Do not publish.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Do not publish.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Do not publish.