Omron NX Series User Manual page 352

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

14 Troubleshooting
Event name
Communications Controller Error
Meaning
A hardware error was detected in the Communications Controller of the Ethernet port.
Source
X Bus Ethernet Function Module
Error attributes
Level
Effects
User program
Indicators
Ethernet NET RUN
OFF
Device variable
Variable
ETN_Port1Status.LanHwErr
ETN_Port2Status.LanHwErr
Cause and cor-
Assumed cause
rection
Hardware failure of Communica-
tions Controller
Attached infor-
None
mation
Precautions/
Once the device variable ETN_Port1Status.LanHwErr or ETN_Port2Status.LanHwErr becomes TRUE, it will
Remarks
not become FALSE unless the Controller power is turned OFF and then ON.
14-16
Source details
Minor fault
Recovery
Continues.
Operation
Ethernet NET ERR
Lights.
Data type
BOOL
BOOL
Correction
Replace the Unit.
Event code
04310000 hex
1 to 4: Mounting
Detection tim-
position of the X
ing
Bus Unit (unit
number) and
communications
port 1/
communications
port 2 are given
in combination
Cycle the power
Log category
supply.
Ethernet communications are not possible for the rele-
vant communications port.
Ethernet LINK/ACT
---
Name
Port1 Communications Controller
Error
Port2 Communications Controller
Error
Prevention
None
NX-series EtherNet/IP Unit User's Manual (W627)
Continuously
System

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx-eip201

Table of Contents