Appendices
The name and size of the tag must be the same as those of the network variable
include the Controller status information in tags for the tag sets. You can also set the data output oper-
ation at a fatal error occurrence for output tags.
Refer to Registering the Tag and Tag Set on page A-14 for information on how to register tags and
tag sets.
*1. A variable with its Network Publish attribute set to Output or Input in the Global Variable Table is called a
network variable.
EtherNet/IP Connection Settings (Connection Display)
Specify the target devices and set their connections.
For each connection, set the following information: Connection Name, Connection I/O Type, I/O, target
device tag set (target variable), originator device tag set (originator variable), Packet Interval (RPI),
and Timeout Value.
Refer to Setting Connections for the Originator Device on page A-17 for information on how to make
connection settings.
Precautions for Correct Use
If you changed the IP address, model, or revision of the target device after making the connec-
tion settings, change the connection settings entirely.
A-10
*1
. Set whether to
NX-series EtherNet/IP Unit User's Manual (W627)