Making The Ethernet/Ip Connection Settings With The Sysmac Studio - Omron NX Series User Manual

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Appendices
A-3-4
Making the EtherNet/IP Connection Settings with the Sysmac
Studio
This section describes the procedure to make the EtherNet/IP connection settings with the Sysmac
Studio.
Here, we take the following system configuration as an example to describe how to set the
EtherNet/IP connection settings.
Example: System that connects the EtherNet/IP port on Controller 1 and the EtherNet/IP port on Con-
troller 2 via Ethernet
• Set the settings so that values in the network variable Net_Out1 allocated for Controller 2 are sent to
the network variable Net_In1 allocated for Controller 1 at the set RPI of 50 ms cycle.
• This example assumes the programs for both Controllers 1 and 2 are registered in the same project.
Originator device
Controller 1
(NX502-1500
and NX-EIP201)
Originator device tag set
Net_In1
Net_In1
Convert the network variable to the tag.
Network variable
(Network Publish attribute: Input)
Net_In1
(Data type: WORD)
Follow the flow below to set the settings to Controllers 1 and 2 for which to establish EtherNet/IP con-
nections.
The required settings for the originator device and the target device are shown below.
A-12
Sysmac Studio
Controllers 1 and 2 are respectively named as follows and registered in the same project.
Controller_1(Controller 1:NX502-1500 and NX-EIP201)
Controller_2(Controller 2:NX502-1500 and NX-EIP201)
Ethenet
Target device tag set
(Tag set)
(Tag)
Network variable
(Network Publish attribute: Output)
Project on the Sysmac Studio
Target device
Controller 2
(NX502-1500
and NX-EIP201)
(Tag set)
Net_Out1
(Tag)
Net_Out1
Net_Out1
(Data type: WORD)
NX-series EtherNet/IP Unit User's Manual (W627)