14 Troubleshooting
Connection status
General
Additional
Status
Status
(hex)
(hex)
01
0107
01
0108
01
0109
01
0110
01
0111
14-56
Source of error
Error code returned from target:
Attempted to close a connection, but that
connection was already closed.
Error code returned from target:
Attempted to open a connection with an
unsupported connection type.
Error code returned from target:
The connection size settings are differ-
ent in the originator and target.
Error code returned from target:
The target was unable to open the con-
nection, because of its operating status,
such as downloading settings.
Error code returned from target:
The RPI was set to a value that exceeds
the specifications.
Handling
Configuration
Configuration
1
2
This error does
This error does
not occur.
not occur.
This error does
Check which
not occur.
connection
types can be
used by the
target.
(Contact the
manufacturer.)
Only multicast
and point-to-
point connec-
tions can be
set.
Check the connection (sizes) set in the originator
and target.
Check whether
Depends on
the tag data
the target's
link is stopped
specifications.
at the target.
(Contact the
(Restart the tag
target device's
data link com-
manufacturer.)
munications
with the soft-
ware switch.)
This error does
Check the tar-
not occur.
get's RPI set-
ting specifica-
tions.
NX-series EtherNet/IP Unit User's Manual (W627)
Configuration
3
This is not an
error because
the connection
is already
closed.
Check which
connection
types can be
used by the
originator. (An
error will occur
if a connection
other than a
multicast or
point-to-point
connection is
set.)
Check whether
the tag data
link is stopped
at the target.
(Restart the tag
data link com-
munications
with the soft-
ware switch.)
Set the origina-
tor's RPI set-
ting to 10 sec-
onds or less.