Omron NX Series User Manual page 397

Machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Connection status
General
Additional
Status
Status
(hex)
(hex)
D0
0001
D0
0002
NX-series EtherNet/IP Unit User's Manual (W627)
Source of error
Error code generated by originator:
The connection operation is stopped.
Error code generated by originator:
The connection is being opened (open-
ing processing in progress).
14 Troubleshooting
Handling
Configuration
Configuration
1
2
The connection
The meaning
was stopped
of this error
because the
code is defined
Tag Data Link
by each ven-
Stop Bit was
dor, so it de-
turned ON, or
pends on the
the settings da-
target's specifi-
ta is being
cations.
downloaded.
(Contact the
Either turn ON
target device's
the Tag Data
manufacturer.)
Link Start
Switch, or wait
until the set-
tings data has
been down-
loaded.
This code in-
cludes fatal
Controller er-
rors and Unit
failure. To han-
dle these er-
rors, refer to
the NJ/NX-
series
Troubleshootin
g Manual (Cat.
No. W503).
Wait until the
The meaning
opening proc-
of this error
essing is com-
code is defined
pleted.
by each ven-
dor, so it de-
pends on the
target's specifi-
cations.
(Contact the
target device's
manufacturer.)
Configuration
3
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
14
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
14-61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx-eip201