Bit
15 to 6
Reserved.
5
This bit indicates whether a minor fault level Controller error has occurred.
TRUE: A minor fault level Controller error has occurred.
FALSE: A minor fault level Controller error has not occurred.
4
This bit indicates whether an observation level Controller error has occurred.
TRUE: An observation level Controller error has occurred.
FALSE: An observation level Controller error has not occurred.
3 to 0
Reserved.
l Functional Classification: NX-series EtherNet/IP Unit Status
Variable name
Meaning
ETN_Port1Status.Et-
Port1 Online
nOnlineSta
ETN_Port2Status.Et-
Port2 Online
nOnlineSta
EIP_Comm1Sta-
CIP Communica-
tus.TDLinkRunSta
tions1 Tag Data Link
Communications Sta-
tus
EIP_Comm2Sta-
CIP Communica-
tus.TDLinkRunSta
tions2 Tag Data Link
Communications Sta-
tus
EIP_Comm1Sta-
CIP Communica-
tus.TDLinkAllRunSta
tions1 All Tag Data
Link Communications
Status
EIP_Comm2Sta-
CIP Communica-
tus.TDLinkAllRunSta
tions2 All Tag Data
Link Communications
Status
NX-series EtherNet/IP Unit User's Manual (W627)
6 Device Variables Related to the NX-series EtherNet/IP Unit
Description
Function
Indicates that the EtherNet/IP port's com-
munications can be used via the commu-
nications port 1 (that is, the link is ON, IP
address is defined, and there are no er-
rors.)
TRUE: The EtherNet/IP port's communi-
cations can be used.
FALSE: The EtherNet/IP port's communi-
cations is disabled due to an error in ini-
tial processing, restart processing, or link
OFF status.
Indicates that the EtherNet/IP port's com-
munications can be used via the commu-
nications port 2 (that is, the link is ON, IP
address is defined, and there are no er-
rors.)
TRUE: The EtherNet/IP port's communi-
cations can be used.
FALSE: The EtherNet/IP port's communi-
cations is disabled due to an error in ini-
tial processing, restart processing, or link
OFF status.
Indicates that at least one connection is
in normal operation in CIP communica-
tions 1.
TRUE: Normal operation
FALSE: Other than the above.
Indicates that at least one connection is
in normal operation in CIP communica-
tions 2.
TRUE: Normal operation
FALSE: Other than the above.
Indicates that all tag data links are com-
municating in CIP communications 1.
TRUE: Tag data links are communicating
in all connections as the originator.
FALSE: An error occurred in at least one
connection.
Indicates that all tag data links are com-
municating in CIP communications 2.
TRUE: Tag data links are communicating
in all connections as the originator.
FALSE: An error occurred in at least one
connection.
Range of
Data type
values
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
Reference
page 6-24
page 6-24
6
page 6-24
page 6-25
page 6-25
page 6-25
6-11