9 Tag Data Link Functions
Drag & Drop
Additional Information
The EtherNet/IP originator device (i.e., a device in which connections can be set) must be one
of the following OMRON EtherNet/IP devices.
Device name
NX-EIP201
CJ1W-EIP21 (NJ)
CJ1W-EIP21
CJ1W-EIP21 (CJ2)
CJ2B-EIP21
CJ2M-EIP21
CS1W-EIP21
NX701
NX502-££££
NX102-££££
NX1P2
NJ501-££££
NJ301-££££
NJ101
Use the following procedure to create connections (i.e., tag data links) by dragging and dropping devi-
ces.
1
Set the tags and tag sets for the target device that will be dragged.
• Refer to 9-2-4 Creating Tags and Tag Sets on page 9-19 for information on the settings if the
target is one of the OMRON EtherNet/IP devices given above.
• If the target is another EtherNet/IP device, refer to the manual of that device and perform
settings as required.
2
A dialog box as in the following figure for connection allocation will be displayed when you drag
the target device and drop it at the OMRON EtherNet/IP device.
• Using One of the Above OMRON EtherNet/IP Devices As Target
9-46
EtherNet/IP port on NX-series EtherNet/IP Unit
CJ1W-EIP21 mounted to NJ-series Controller
CJ1W-EIP21 mounted to CJ1 CPU Unit
CJ1W-EIP21 mounted to CJ2 CPU Unit
Built-in EtherNet/IP port in CJ2H CPU Unit
Built-in EtherNet/IP port in CJ2M CPU Unit
CS1W-EIP21 mounted to CS1 CPU Unit
Built-in EtherNet/IP port on NX-series CPU Unit
Built-in EtherNet/IP port on NJ-series CPU Unit
Remarks
NX-series EtherNet/IP Unit User's Manual (W627)