5-6

SNMP Settings Display

 SNMP Service
Setting
SNMP Service
Port No. *
Address
Location
Send a recognition trap
* The following ports are used by the system and cannot be set by the user: 53, 68, 123, 162, 2222, 9600, and
44818.
Additional Information
Refer to Section 11 SNMP Agent for details on the SNMP service.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
5 Sysmac Studio Settings for the EtherNet/IP Unit
Description
Specify whether to use the SNMP monitor service.
If not using the SNMP monitor service is specified, an SNMP manager cannot connect
from an external device.
Set the port number to use to connect to the SNMP server that is used to connect from
an SNMP manager.
It is normally not necessary to change this setting.
Set the communications device administrator name and installation location as text
information. You do not necessarily have to input all items. This information is read by
the SNMP manager. (You can input up to 200 alphanumeric characters for each item.)
Set whether to send an authentication trap.
If you select Send a recognition trap and there is access from an SNMP manager that
is not set in Recognition 1 or Recognition 2, an authentication trap is sent to the SNMP
manager.
If you select Send a recognition trap, specify the SNMP trap settings on the SNMP Trap
Tab Page.
5
Default
Do not use.
0 (port No. 161)
None
None
Not selected. (Not
used.)