Event name
SNMP Setting Error
Meaning
A setting error in SNMP agent/trap was detected.
Source
X Bus Ethernet Function Module
Error attributes
Level
Effects
User program
Indicators
Ethernet NET RUN
---
Device variable
Variable
None
Cause and cor-
Assumed cause
rection
Parameter error
Power interruption while download-
ing SNMP agent/trap settings
Memory error
Attached infor-
Attached information 1: Error type
mation
01 hex: Non-volatile Memory Access Error, 02 hex: There is an inconsistency in the set values.
Attached information 2: Error Location
If there is an inconsistency in the set values:
01 hex: SNMP agent settings, 02 hex: SNMP trap settings
Precautions/
None
Remarks
NX-series EtherNet/IP Unit User's Manual (W627)
Source details
Minor fault
Recovery
Continues.
Operation
Ethernet NET ERR
Flashes at 1-s intervals.
Data type
---
Correction
Identify the cause of the error from
the attached information, correct
the settings, and then download
the settings again.
Clear all memory or download the
settings again.
If the above measures do not work,
replace the Unit.
14 Troubleshooting
Event code
36060000 hex
1 to 4: Mounting
Detection tim-
position of the X
ing
Bus Unit (unit
number) and
SNMP are given
in combination
Automatic re-
Log category
covery (after
downloading the
SNMP settings),
cycle the power
supply, or Con-
troller reset
SNMP operation stops.
Ethernet LINK/ACT
---
Name
---
Prevention
None
Do not turn OFF the power supply
to the Controller while the SNMP
agent/trap settings are being down-
loaded.
None
At power ON or
Controller reset
System
14
14-21