Internal Raid/Hba/Expander Adapter Replacement - Lenovo ThinkSystem SR650 V3 7D75 User Manual

Hide thumbs Also See for ThinkSystem SR650 V3 7D75:
Table of Contents

Advertisement

• Go to
https://datacentersupport.lenovo.com/products/servers/thinksystem/sr650v3/7d75/downloads/driver-
to see the latest firmware and driver updates for your server.
list/
• Go to
"Update the firmware" on page 445
Watch the procedure
A video of this procedure is available at YouTube:
BmyijyY0-lNvapM4fTV5Gf
Procedure
Step 1.
Install the Torx T30 nut.
Figure 80. Installing a Torx T30 nut into the heat sink
Note: Do not touch the gold contacts on the bottom of the processor.
a.
Rotate the anti-tilt wire bail inwards.
b.
Orient the Torx T30 nut under the anti-tilt wire bail; then, align the Torx T30 nut with the
socket at an angle as shown.
c.
Push the lower edge of the Torx T30 nut into the socket until it clicks into place. Make sure
the Torx T30 nut is secured under the four clips in the socket.
After you finish
1. Reinstall the PHM. See
2. Complete the parts replacement. See

Internal RAID/HBA/expander adapter replacement

Use this information to remove and install an internal customer form factor (CFF) RAID adapter, internal CFF
HBA adapter, or internal CFF RAID expander adapter.
for more information on firmware updating tools.
.
"Install a processor and heat sink" on page
"Complete the parts replacement" on page
https://www.youtube.com/playlist?list=PLYV5R7hVcs-
183.
.
Chapter 5
Hardware replacement procedures
269.
119