Lenovo 7D9F Manual page 38

Messages and codes reference
Hide thumbs Also See for 7D9F:
Table of Contents

Advertisement

Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0490
User Action:
Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan or cooling related issues and address them first.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place and keep clean.
3. Make sure that the room temperature meets operating specifications.
4. Upgrade all system firmware and chassis firmware (if applicable) to the latest level.
5. If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.
• FQXSPCA0009M: Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0494
User Action:
Complete the following steps until the problem is solved:
1. Make sure the data center Temperature environment is within 47°C degree.
2. Make sure there is no hot air in front of the affected system.
3. If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.
• FQXSPCA0011N: Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted.
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0498
User Action:
Complete the following steps until the problem is solved:
1. Make sure the data center Temperature environment is within 50°C degree.
2. Make sure there is no hot air in front of the affected system.
3. If the problem persists, collect service data log from the XCC WebGUI and contact Lenovo Support.
• FQXSPCA0012I: Sensor [SensorElementName] has transitioned to normal state.
34
ThinkSystem SR655 V3 Messages and Codes Reference