3. Central Controller(YJE-C01T(E))
Operation Modes of Central Controller
1. Group Control Mode (for the control of all conditioners in the central control network)
To control the air conditioners in the group in a unified manner.
2. Zone Control Mode
To control the air conditioners in the zone in a unified manner.
Before central control, group/zone settings must be carried out.
Group Setting
If the centralized controller at the next higher level is used,
group setting needs to be carried out. The group number is only
effective for the centralized controller.
All conditioners in the central control network can be classified
into a range of group 1 to group 128.
Setting method:
Hold down "ADD. FUNC." button under shutdown state for 3
seconds to enter group setting, "GROUP" indicator and
group number blink. Press "
number. Press "ENTER" button to confirm the set group number,
press "CANCEL" button to cancel.
Zone Setting
In a central control network, a maximum of 16 zones can be set.
The same unit can be classified into different zones. A maximum
of 16 air conditioners can be set in one zone.
1. Hold down "Zone" button for 3 seconds to enter zone
setting, and the zone number blinks. Press "
select the zone number. Press "ENTER" button to enter
setting of this zone.
2. Press "
" or "
" to select the air conditioner address
numbers from 1 to 16, and the number blinks. Press "ENTER"
button to confirm the selected number which is underlined.
Press "CANCEL" button to cancel.
3. Press "Zone" button to enter setting of the next zone.
A maximum of 16 zones can be set.
4. Press "Zone" button again to exit the zone setting.
Group Control (Full Control)
1. After entering the group control mode, you can perform as
follows:
Press "Group" button repeatedly until the group number and
addresses of all air conditioners in the group are displayed
on the central controller.
As shown in the right figure, the group number is 1, and there
are 16 air conditioners in this group.
2. Unified function setting can be performed by other buttons
(for detail description, please refer to instructions for specific
operation procedure).
" or "
'' to select the group
" or "
82
ADD. FUNC.
TIMER/CLOCK
SWING
CANCEL
Group
Group indicator
number
3
ADD. FUNC.
TIMER/CLOCK
SWING
CANCEL
3
'' to
Air conditioner
Zone
address
number
Setting completed
Full unified control
ON/OFF
ENTER
MODE
FAN
ZONE
ON/OFF
ENTER
MODE
FAN
2
ZONE
1
Zone selection
Unit selection