Hisense YXE-A03U Technical & Service Manual page 107

Wired controller/central controller/control box
Table of Contents

Advertisement

4.
Control BOX (B544(E))
MODEBUS Protocol
4
1.Function code
Address code: The address code is set by the DIP switch.
Function code: The function code is as follows:
01
02
03
04
05
06
2. Definition of registers
(1) Instruction of the registers
Coil and Hold Registers are for setting air conditioner parameters.
Discrete Inputs and Input Registers are for reading air conditioner status.
(2) Definition of registers as follows:
No.
00001
00002
00003
Electric heater status
00004
Energy-saving status
00005
00006
Compressor status
00007
00008
No.
Object
00001
Indoor temperature
The setting
00002
temperature
00003
Mode
00004
Fan speed
00005
Swing
00006
Outlet air
00007
temperature
Code
Read Coils
Read Discrete Inputs
Read Holding Registers
Read Input Registers
Write Single Coil
Write Single Holding Register
Read Discrete Inputs (Code 0x02)
Object
Type
ON/OFF status
BI
Sleep status
BI
BI
BI
Defrost status
BI
BI
Super mode
BI
Mute mode
BI
Read Input Registers (0x04)
Type
Reg Addr
AI
0001
AI
0002
MI
0007
MI
0008
MI
0009
Fault
MI
0012
AI
0015
Function
Addr
0000
0-OFF/1-ON
0003
0-OFF/1-ON
0004
0-OFF/1-ON
0009
0-OFF/1-ON
0010
0-No/1-Yes
0011
0-OFF/1-ON
0014
0-No/1-Yes
0015
0-No/1-Yes
Value
-20-79
18-32
FAN=00;HEAT=01;
COOL=02;DRY=03;
AUTO CODE=05;
AUTO HEAT=06
AUTO FAN=07;
AUTO=00;HIGH=01
MIDDLE=03;LOW=02
NO SWING=0;
LEFT/RIGHT=1;
UP/DOWN=2;
UP/DOWN/LEFT/RIGHT=3
1-255
-20-79
105
Value
Comment
Comment
See Error Code table