Hisense YXE-A03U Technical & Service Manual page 115

Wired controller/central controller/control box
Table of Contents

Advertisement

4.
Control BOX (B544(E))
Object List
6
Device Instance: 10000 + Set address
Device MSTP MAC address:16+ Set address
Set address: Set at B544 dip switch
For example:
If the B544(E) dip switch address set to 2, this B544(E) in BACnet MSTP
Device Instance should be 10002, and the MAC address should be 18.
No.
Object
Indoor
1
Temperature
Set
2
Temperature
No.
Object
ON/OF
1
Status
2
SLEEP Status
3
ELECTRICAL
No.
Object
1
Mode
2
Fan
3
Swing
4
Error
No.
Object
Set
1
Temperature
2
Set Humiduty
Alog input object
Object
Type
Instance
AI
000001
AI
000002
Binary input object
Object
Type
Instance
BI
000000
BI
000003
BI
000004
Multistate input object
Object
Type
Instance
MI
000001
MI
000002
MI
000003
MI
000006
Analog valve object
Object
Type
Instance
AV
000000
AV
000001
113
Value
Comment
-20-79
18-32
Value
Comment
0-Off/1-On
0-No/1-Yes
0-No/1-Yes
Value
= 00
FAN
= 01
HEAT
= 02
COOL
= 03
DRY
= 04
AUTO
= 00
AUTO
= 01
HIGH
= 03
MIDDLE
= 02
LOW
NO SWING=0
UP/DOWN
= 1
LEFT/RIGHT
= 2
UP/DOWN/LEFT/RI
= 3
GHT
1-255
Value
18-32
0-100%
Comment
See Error
Comment
Reserved