Hisense YXE-A03U Technical & Service Manual page 13

Wired controller/central controller/control box
Table of Contents

Advertisement

2. Wired Controller(YXE-A03U(E))
Indoor Unit Parameter Setting
The internal parameters of the air conditioner can be set with the following method
Instruction
1. Hold down Mode button and Fan button for 3s simultaneously to enter parameters customer-
reading state, then customer-reading parameter codes will display in temperature display area.
(See fig. 4)
2. Press Up or Down button to adjust to the customer-setting parameter code 17, press timer button to
enter the state to set this parameter, then its function code will flicker. (See fig. 5)
3. Press Up or Down button to adjust to the detailed customer-setting parameter code to set. Press timer
button to enter the detailed state to set this parameter. For detailed information, please refer to
Table 2. For example, the picture below means that it is to open self-recovery function by changing
EE 00 to EE 01. (See fig. 6)
4. Press ON/OFF button to quit customer-reading state to #17, then press ON/OFF button to quit
customer-setting state.(See fig. 7)
fig. 4
fig. 6
fig. 7
fig. 5
11
.