Wired controller/central controller/control box
Table of Contents

Advertisement

2. Wired Controller(YXE-C01U1(E))
Parameter
Parameter Description
Code
Self recovery of power
1
break
2
Temperature type
Temperature display
3
type
Ratio of ambient
temperature sensed by
4
indoor temperature
sensor(cooling mode)
5
Filter clean indication
6
Filter clean time set
Installation height
7
compensation
Cooling temperature
8
compensation(indoor
unit temperature sensor)
Heating temperature
9
compensation(indoor
unit temperature sensor)
10
Static pressure set
Ratio of temperature
sensed by indoor
12
temperature
sensor(heating mode)
Temperature adjustment-
13
cooling
Temperature
14
adjustment-heating
Access control, fire
protection, ON/OFF
25
function set
Table 2
Parameter Value&Representation
Data Type
Representation (Function Code)
0: Cancel self recovery of power break
function;
Integer
1: Self recovery of power break;
others: invalid.
0: Centigrade temperature;
Integer
1: Fahrenheit temperature;
others: invalid.
0: Default display set temperature;
Integer
1: Default display room temperature;
others: invalid.
0~10valid, more than 10default is 10
Integer
0:0%; 1:10%;...;10:100%
0: Default display set temperature
Integer
1: Default display room temperature
others: invalid
Integer
0~32, more than 32 default is 32*1000h
0~10m, more than 10m default is 10.
=0,1,2: no fan speed compensation
Integer
=3: increase fan speed
=4~10: increase more fan speed
0: 0℃;1:-0.5℃;2:-1℃;3:-1.5℃;4:-2℃;
5:-2.5℃;6:-3.0℃;7:-3.5℃;8:-4℃;9:-4.5℃;
Integer
10:-5℃ (the wired controller displays
integer with symbol)
0: 0℃;1:-0.5℃;2:-1℃;3:-1.5℃;4:-2℃;
5:-2.5℃;6:-3.0℃;7:-3.5℃;8:-4℃;9:-4.5℃;
Integer
10:-5℃ (the wired controller displays
integer with symbol)
1~250, function code=static pressure
more than the limit static pressure default
Integer
the limit static pressure, default is
0 (default static pressure, related to
models)
0~10valid, more than 10 default is 10
Integer
0:0%; 1:10%;...;10:100%
Character -10~10℃ (single character with symbol)
Character -10~10℃ (single character with symbol)
=0, access control, fire protection
functions are all invalid;
=1, access control function is valid;
Integer
=2, fire protection function is valid;
=3, access control, fire protection are all
valid;
=4, ON/OFF function are all valid.
28
NOTE
0:entirely use temperature
sensed by wired remote
controller;
10:entirely use temperature
sensed by indoor unit
Duct type(DC motor)
0:entirely use temperature
sensed by wired remote
controller;
10:entirely use temperature
sensed by indoor unit
Temperature displayed on
wired controller
Temperature displayed on
wired controller