Hisense YXE-A03U Technical & Service Manual page 62

Wired controller/central controller/control box
Table of Contents

Advertisement

2. Wired Controller(YXE-E01U(E)/YXE-E02U(E))
Read and write EEPROM parameters of indoor unit
The internal parameters of the air conditioner can be set with the following method
Instruction
1.
Press and hold the "
for 3s at the same time to enter the parameter
self-setting state, Then the "
icon will be always on.
2.
Press the "
" / "
or decrease the root address as 3.
3. Press the "
" / "
decrease the sub-address, and select the desired
sub-address value.
4.
Press the "
"/ "
" button to confirm.
and press "
5.
Press the "
" button to exit without settings.
The catalogue of Read and write EEPROM parameters is shown as follows:
Sub-address
Parameter description
parameter code
Self-recovery of power
01
break
02
Temperature type
Temperature display
03
type
Ratio of indoor unit
body temperature
04
(cooling mode)
05
Filter clean indication
06
Filter clean time set
Installation height
07
compensation
Cooling temperature
08
compensation(indoor
unit temperature sensor)
Heating temperature
09
compensation(indoor
unit temperature sensor)
10
Static pressure set
" and "
" button
" and "
" button to increase
" button to increase or
" button to set parameters,
Parameter Representation (Function Code)
0: Cancel self-recovery of power break function;
1: Self recovery of power break; others: invalid.
0: Centigrade temperature;
1: Fahrenheit temperature;
others: invalid.
0: Default display set temperature;
1: Default display room temperature; others: invalid.
0~10valid, more than 10default is 10 0:0%;
1:10%;...;10:100%
0: Default display set temperature
1: Default display room temperature others: invalid
0~32, more than 32 default is 32*1000h
0~10m, more than 10m default is 10. =0,1,2: no fan
speed compensation
=3: increase fan speed
=4~10: increase more fan speed
0: 0℃;1:-0.5℃;2:-1℃;3:-1.5℃;4:-2℃; 5:-2.5℃;6:-
3.0℃;7:-3.5℃;8:-4℃;9:-4.5℃; 10:-5℃ (the wired
controller displays integer with symbol)
0: 0℃;1:-0.5℃;2:-1℃;3:-1.5℃;4:-2℃; 5:-2.5℃;6:-
3.0℃;7:-3.5℃;8:-4℃;9:-4.5℃; 10:-5℃ (the wired
controller displays integer with symbol)
0~240, function code=static pressure more than
the limit static pressure default the limit static
pressure.
"
root address+ sub-address+
3
root address- sub-address-
YXE-E01U(E)
60
.
Parameters value code
root address sub-address
sub-address+
root address+
1
4
3
root address- sub-address-
YXE-E02U(E)
NOTE
0: entirely use temperature
sensed by wired remote
controller;
10:entirely use temperature
sensed by indoor unit
1
4