Hisense Hi-Dom Installation, Configuration And Maintenance Manual
Hisense Hi-Dom Installation, Configuration And Maintenance Manual

Hisense Hi-Dom Installation, Configuration And Maintenance Manual

Advertisement

Quick Links

Hi-Dom
Installation Configuration and
Maintenance Manual

Advertisement

loading

Summary of Contents for Hisense Hi-Dom

  • Page 1 Hi-Dom Installation Configuration and Maintenance Manual...
  • Page 2 Preamble ●This product is air-conditioning centralized monitoring and management system Hi-Dom. The system includes air-conditioning adapter, meter concentrator and service software. ●This air-conditioning adapter requires server (server installed with software which should be bought from field sales) in concert with Ethernet or Internet for use.
  • Page 3 1.1 Connection scheme The connection scheme of this system is shown in Figure 1.1. This manual only describes the installation and configuration of Hi-Dom system, for other units in the system, please refer to the respective operating instructions supplied. Figure 1.1 Connection scheme ※One air-conditioning management server can connect up to 32 air-conditioning adapters.
  • Page 4 Figure 1.2 LED indicators 1.2.1 Description of LED indicators POWER Power display LED (red) it is on when the unit is power-on H-NET Air-condition side communication flashing when a signal is transmitted display LED (yellow) from H-NET system working status display (green) it is on when initialization and flashing during normal operation 485TX...
  • Page 5 Figure 1.3 Terminal marking diagram 1.2.2 Terminal marking instruction ① : Power input(DC12V)-------------Non-polarized ② : Power input(DC12V)-------------Non-polarized ③ : H-NET signal input ---------------Non-polarized ④ : H-NET signal input ---------------Non-polarized ⑤ : RS485 A ----------------------------positive ⑥ : RS485 B ----------------------------negative ⑦ :USB(DC5V) ⑧...
  • Page 6 Communication objects Air-condition outdoor unit and indoor unit Communication wiring Non-polarized 2 core wire Communication mode Half-duplex communication Communication synchronous asynchronous communication mode Communication speed 9600 bps Wiring distance Total length less than 1000m Number of air conditioners 128 indoor units connected Table 1.3 LAN(Ethernet) Communication Specification Item...
  • Page 7 2.2 Installation and wiring instructions (1) Air Conditioning adapter and meter adapter needs to be installed in the weak current control cabinet with screws for vertical mounting and guide rail for horizontal installation, in case of vertical installation with screws, certain gap is to be left for 30~50mm wiring around the adapter. (2) Communication and power supply terminals are barrier terminal blocks, rotate the terminals counterclockwise with appropriate Phillips screwdriver, then insert the wire into the terminal and rotate the terminal clockwise, wire installation is complete.
  • Page 8 micro USB DC 5V For power supply to Within wiring Data Collector, optional LAN wiring IEEE 802.3 For communication Within LAN(UTP-five) standard with management 100m server, a must-have 3. System installation configuration and debugging 3.1 Service software installation ※ service software latest version can be downloaded from the website www.achelp.cn, username: admin, password: admin.
  • Page 9 Figure 3.2 Installation completion interface After installation is completed, login screen is automatic pop-up as shown in Figure 3.3, click on <Set the default browser> in the page, this browser is set as the default browser, a shortcut login system will be automatically created on the desktop. The default username of this system is admin, password is admin.
  • Page 10 The so-called same network segment refers to the first 3 segments of the IP address are the same(subnet mask: 255.255.255.0 is supposed),, for example, the first three segments of 192.168.1.2 and 192.168.1.101 are “192.168.1”, so 192.168.1.101 and 192.168.1.2 are in the same network segment.
  • Page 11 Figure3.5 Setting and debugging Click <Network Settings> into the IP settings interface, as shown in Figure 3.6 (other options have nothing to do with IP address setting, do not change, otherwise it will lead to consequences of unable to return!) Figure 3.6 Network Settings screen 5.
  • Page 12 setting the IP address, the new IP address must be marked on a tag attached to the adapter to facilitate future maintenance. ※ Pay attention to the sequence of this operation, first set the computer’s Local IP, then wait until the adapter is in the normal working state (“RUN” indicator flashes, without considering other indicators), then connect the computer to the air conditioning adapter with a network cable.
  • Page 13 3.4 can be omitted 3.4.1 Adding air conditioning adapter View Hi-Dom system login page and log into the system to enter <check debugging> -> <air-condition adapter maintenance>, click <add records> button to add air conditioning adapters, after adding and editing is completed, click <save added records> to save, for changes, double-click the left mouse button to modify the content, and click <to save the change record>...
  • Page 14 “MAC ” here is “air conditioning Adapter ID”, it can be copied for use. Repeat this operation to add all air conditioning adapters into Hi-Dom system After all adapters are added and saved successfully, click <read time> to read adapter time, and click <timing>...
  • Page 15 total of 32 numbers, which is not changed after leaving factory. In the Adapter Configuration main interface, click <Production Information> to enter the factory information interface, as shown in Figure 3.12: Figure3.12 Factory information interface of M-Concentrator 3.4.3 Air conditioning connection search and save After all air-conditioning adapters and meter reading adapters are added, click <Search>...
  • Page 16 Increase progressively according to the Required table (figure larger than 1) GW_ID Air conditioner adapter mac address (32 Required digits) can be obtained from nameplate on back of the adapter or form the adapter’s inner web configuration page GW_Line NO. Adapter Serial No.
  • Page 17 reading multiplied by multiple of ratio of transformation. Meter GW_ID Meter Reading Adapter mac Address (32 Optional (Fill when Digits) can be obtained from nameplate on connecting electricity meter) back of the adapter or form the adapter’s inner web configuration page Meter GW _ Meter Reading Adapter Serial No.
  • Page 18 Note: If air conditioner connection information table is prepared and perfected before installing Hi-Dom system, all steps in 3.4 can be directly skipped and it just needs to lead in the installation information configuration table from here. 3.6 Issue electricity meter address Enter into the <Inspection and Debugging>-><Electricity Meter and Gas Meter...
  • Page 19 Fig. 3.16 Electricity Meter Maintenance Page Fig. 3.17 Complete issuing configuration of electricity meter address 4. Air Conditioner Adapter Power Supply Input 4.1 Power Supply Input (1) Firstly, confirm that power normal (DC 12V),H-NET and LAN connection is normal, then supply power to the machine. (2) When power supply is input, POWER light of adapter is lightened normally (power supply indicator) and RUN light (operation indicator) is lightened normally until air conditioner searching is completed when the RUN light will start flickering.
  • Page 20 4.3 Normal/Abnormal Display Refer Table 4.1 for normal/abnormal display of working conditions of the machine Table 4.1 Normal/abnormal display Expressed Lighting Conditions Lighting-off Conditions Name Item POWER Power Power on Power off working · Often lighting when the · Lighting and dying conditions of machine implements air flickering in frequency of 0.5...
  • Page 21 power supply. server is set correctly. ip address into the same segment. Check whether ip address of Log in air conditioner and meter server is set correctly on the air reading adapter configuration page conditioner and meter reading and confirm ip address adapter configuration page.
  • Page 22 Check whether IP address for air Initial IP address of the machine is conditioner dedicated server is in 192.168.1.101. Please check the same segment with IP address network conditions with common of the machine. Check whether PC instead of the machine. PING to the machine from the management server is available.
  • Page 23 Changes will be made for product improvement and other reasons without notice. Customer Service Dept. Add.: Hisense Building, No. 17, Donghaixilu, Qingdao Qingdao Hisense Hitachi Air Conditioner System Co., Ltd. Add.: No. 218, Qianwanganglu, Qingdao Economic and Technological Development Zone...
  • Page 24 Meter current MeterGW_ GW_ID Line Building Floor Room Tenant Tenant_NO IU_model OU_Alias OU_model standby Meter GW_ID OU_meter1 transformer address address capacity line_NO Power(× 1W) coefficient 0be0ff12400429aef9a46c52871e00f5 Room_A101 RPI-28FSN6Q AC_OU_1 RAS-560FSN6Q ffffffffffffffffffffffffc0a88a69 3789654 0be0ff12400429aef9a46c52871e00f5 Room_A102 Antonio RPI-28FSN6Q AC_OU_1 RAS-560FSN6Q ffffffffffffffffffffffffc0a88a69 3789654 0be0ff12400429aef9a46c52871e00f5 Room_A103 Jacob...