3. Central Controller(YXE-C03U(E))
Parameter Setting
1.Ambient Temperature Correction
(The adjustment can only be done when the environment temperature
modification setting is available, and for details, see the part of
)
Setting of ambient temperature correction is for
particular cases (e.g. installation location near the
marble wall): wired remote controller is set to
display ambient temperature, but the ambient
temperature detected is different from the actual
room temperature, and setting correction is
necessary.
确 定
1
2
Ambient temperature correction
Setting method:
1. Under OFF conditions, press the "
button to display the
2. Hold down the "ADD.FUNC" for 3s, the buzzer
will beep for four times to alert that it goes into the
environment temperature modification state. The
environment temperature value and environment
temperature icon
flicker at the same time.
3. Press the "
" (plus) button or "
button to adjust the environment temperature
value within the range of ±20℃ of the current
temperature, press the "ENTER" button to confirm
the setting, save the setting and exit.
How to cancel:
Under ambient temperature correction mode,
press "CANCEL" button to cancel correction and
exit.
Press any other button (except MODE button) to
exit ambient temperature correction directly.
2
3
" or "
"
icon.
" (minus)
2.Temperature Limit Setting
Default temperature range is (16-30)℃. You can
change the range when needed.
For example, in cooling mode, temperature
adjustment range could be changed to (23-30)℃;
in heating mode, it could be changed to (16-23)℃.
The temperature limit is only effective for the
cooling and heating modes.
Setting method:
1. If the temperature limit is allowed to be modified
(for detailed operations, see
can press the " " (plus button) or " " (minus
button) to adjust the wire remote controller to
display
.
2. Hold down the "ADD.FUNC" button for 3s, and
the buzzer will beep four times to alert that it goes
into the setting temperature limit state. The wire
remote controller's limit temperature and limit
temperature numerical value icons will flicker.
3. Press the " " button (plus) or " " button (minus)
to adjust the temperature limit value within the
range of 18-32, and if you press the "MODE"
button, it will change in the following sequence:
COOLING
DRYING
Press "ENTER" button to save the change and
exit. After setting the limit temperature and limit
temperature numerical value icons stop flickering.
How to cancel:
Under the state of temperature limit setting, press
the "CANCEL" button to cancel setting and exit.
Press any other button (except the MODE button)
to exit from the temperature limit setting directly.
3.DIP switch setting
Please set the DIP code based on the practical
situations, which will work if it is dialed before power on.
NOTE:
The symbol "
" represents the position where the
DlP code locates.
Dial code Dial content
Terminal
SW16-1
resistance
setting
Fuse short-
SW16-2
circuit setting
78
HEATING
FAN
AUTO
ON
OFF
3 4
SW16
Setting method
In order to guarantee the communication
speed, it must be set as ON if being at the
both ends of integrated control system.
After the fuse on electric control board
blows, you can dial the dial code to ON to
restore the integrated control
communication.
), you