Wired controller/central controller/control box
Table of Contents

Advertisement

2. Wired Controller(YXE-E01U(E)/YXE-E02U(E))
Parameter setting
The wired controller room temperature display, limit set temperature, maximum quantity of central
control and address can be revised if needed. Before setting, please check if these parameters are
enabled to be revised, for details, see Custom parameters.
Temperature limit setting
Default temperature range is (16-30)℃. You can change the
range when needed. For example, in cooling mode,
temperature adjustment range could be changed to (23-30)
℃, in heating mode, it could be changed to (16-23)℃.
Setting method:
1. During OFF conditions, press and hold the "
at the same time for 3s to enter parameter setting mode, and the
icon
will be displayed on the LCD.
2. Press the "
" / "
within the range of (16-30)℃.
3. Press the "
" button to confirm the setting, or wait for 5s,
save the setting and exit.
How to cancel:
Press the "
" button to exit without settings.
NOTE
:
Temperature limit setting function is valid for cooling and heating modes.
Room temperature correction
Setting of room temperature correction is for particular cases (e.g. installation location near the marble wall):
wired controller is set to display room temperature, but the room temperature detected will be different from the actual room
temperature, so setting correction is necessary.
Setting method:
1. During OFF conditions, press and hold the "
the same time for 3s to enter parameter setting mode, and the icon
will be displayed on the LCD.
2. Press the "
" / "
within an offset of -20~20℃ of the current temperature.
3. Press the "
" button to confirm the setting, or wait for 5s, save the
setting and exit.
How to cancel:
Press the "
" button to exit without settings.
NOTE
:
Room temperature correction function is valid for cooling and heating mode.
" button to adjust the temperature limit value
" button to adjust the room temperature value
" and "
" buttons
" and "
" buttons at
YXE-E01U(E)
58
Temperature limit value
YXE-E01U(E)
YXE-E02U(E)
Room Temperature correction value
Offset value
YXE-E02U(E)