Wired controller/central controller/control box
Table of Contents

Advertisement

2. Wired Controller(YXE-C02U1(E))
Parameter Setting
The wired controller room temperature display, limit
set temperature, maximum quantity of central control
and address can be revised if needed. Before setting,
please check if these parameters are enabled to be
revised, for details, see Custom parameters.
1.Room Temperature Correction
Setting of room temperature correction is for
particular cases (e.g. installation location near the
marble wall): the wired controller is set to display the
room temperature, but the room temperature
detected is different from the actual room temperature,
so setting correction is necessary.
2
1
.
.
ADD
FUNC
TIMER/CLOCK
SWING
CANCEL
2
Room Temperature Correction
Setting method:
1. Under the OFF conditions, press "
button to display the
2. Hold down the "ADD.FUNC." for 3s, the buzzer
will beep for four times to alert that it goes into the
room temperature modification state. The room
temperature value and icon
same time.
3. Press "
" (plus) button or "
button to select the room temperature value within
an offset of ±10℉/℃ of the current temperature,
press the "ENTER" button to confirm the setting,
save the setting and exit.
How to cancel:
In room temperature correction mode,
press "CANCEL" button to cancel correction and
exit.
Press any other button (except MODE button) to
exit room temperature correction directly.
2.Temperature Limit Setting
Default temperature range is (61-86)℉[(16-30)℃].
You can change the range when needed. For
example, in cooling mode, temperature adjustment
range could be changed to (73-86)℉[(23-30)℃]; in
heating mode, it could be changed to (61-73)℉[(16
-23)℃]. The temperature limit is only effective for the
cooling and heating modes.
ON/OFF
ENTER
FAN
MODE
3
SLEEP
" or "
"
icon.
start flickering at the
" (minus)
Setting method:
1. UnderOFF conditions, Press down the "
button) or "
" (minus button) to adjust the wired
controller to display
2. Hold down the "ADD. FUNC." button for 3s, and the
buzzer will beep for four times to alert that it goes into
the setting temperature limit state. The wired remote
controller's limit temperature value and icon will flicker.
3. Press the "
" button (plus) or "
to adjust the temperature limit value within the range
of (61~86)
[(16-30) ], and if you press the "MODE"
button, it will change in the following sequence:
COOLING
DRY
Press "ENTER" button to save the change and exit.
After setting, the limit temperature icon and numerical
value icons stop flickering.
How to cancel:
Under the state of temperature limit setting, press the
"CANCEL" button to cancel setting and exit. Press any
other button (except the MODE button) to exit from the
temperature limit setting directly.
2
1
.
.
ADD
FUNC
FAN
TIMER/CLOCK
SWING
ENTER
3
CANCEL
2
Setting of maximum quantity
under integrated control
3.
Setting of Maximum Quantity of Central Control
It is used to set the maximum quantity under central control.
1. Under OFF conditions and if there is no RTC setting,
you can press the " " (plus button) or " " (minus button)
to adjust till the wired remote controller displays the
integrated control icon
2. Hold down the "ADD.FUNC." button for 3s, the buzzer will
beep to alert that it enters the modification setting state, and
the LCD will show the cental control icon
control quantity
3. Press the " " button (plus) and " " button (minus) to
adjust, the cental control quantity setting range is 1-128,
and after pressing the "ENTER" button to confirm the setting,
the
icon and central control quantity icon will stop
flickering, indicating that the setting is completed.
How to cancel:
Press "CANCEL" button in address setting mode to cancel
correction and exit.
Press any other key to exit address setting directly.
46
.
" button (minus)
FAN
HEATING
2
1
.
.
ON/OFF
ADD
FUNC
MODE
TIMER/CLOCK
SWING
ENTER
SLEEP
CANCEL
2
Address setting
.
and central
is flickering.
" (plus
AUTO
ON/OFF
FAN
MODE
3
SLEEP

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Hisense YXE-A03U

Table of Contents