Jnp10K-Pwr-Dc2 Power Supply - Juniper PTX10004 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX10004:
Table of Contents

Advertisement

CAUTION:
the system, or as per local electrical code.
Table 14: DIP Switch Settings for JNP10K-PWR-AC2 Power Supplies
INP0 (Switch 1)
INP1 (Switch 2)
On
On
On
On
On
Off
Off
On
On
Off
Off
On
CAUTION:
power supply to AC mains before loading the system with power.

JNP10K-PWR-DC2 Power Supply

The JNP10K-PWR-DC2 power supply provides two power supplies in a single housing that accepts either
60 A or 80 A using four redundant input power feeds. The two internal power supplies (PS_0 and PS_1)
each have redundant input feeds: A0 and/or B0 for PS_0 and A1 and/or B1 for PS_1. You configure the
input using a set of three DIP switches on the power supply faceplate that sets the combined output power
for both internal power supplies. The output depends on the settings of these DIP switches. See
Table 15 on page 57
and
Use a 2-pole circuit breaker rated at 25 A in the building installation and
H/L (High Input 30 A/
Low Input 20 A)
On (30 A)
Off (20 A)
On (30 A)
On (30 A)
Off (20 A)
Off (20 A)
It is important to connect both input feeds of the JNP10K-PWR-AC2
Figure 20 on page
57.
Output Power
5500 W
3000 W
5000 W
5000 W
2700 W
2700 W
56

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ptx10004-base3Ptx10004-prem2Ptx10004-prem3

Table of Contents