Remove a JNP10K-PWR-DC2 Power Supply

CAUTION:
up to 158°F and 176°F (70°C to 80°C) under running conditions. In order to avoid
injury, do not touch a running power supply with your bare hands.
CAUTION:
sufficient to power the router left in the chassis. See
page 89
Before you remove a DC power supply from the router:
Ensure that you understand how to prevent ESD damage. See
Damage" on page
298.
Ensure that you have the following parts and tools available to remove a JNP10K-PWR-DC2 power
supply:
Heat-protective gloves able to withstand temperatures between 158°F to 176°F (70°C to 80°C)
Electrostatic discharge (ESD) grounding strap
Phillips (+) screwdriver, numbers 1 and 2
13/32 in. (10 mm) nut driver or socket wrench
Replacement power supply or a cover for the power supply slot
CAUTION:
is operational. Either replace the power supply promptly or install a cover over the
empty slot.
To remove a JNP10K-PWR-DC2 power supply from a PTX10004 router:
A working JNP10K-PWR-DC2 power supply can reach temperatures of
Before you remove a power supply, ensure that you have power supplies
and
"Power Requirements for PTX10004 Components" on page
Do not leave the power supply slot empty for a long time while the router
"PTX10004 Power Planning" on
"Prevention of Electrostatic Discharge
192
89.