Turning Outputs On/Off; Setting The Date And Time; Walk Test Mode; Event Memory Recall Mode - Bosch ICP-CC408 Installation Manual

Table of Contents

Advertisement

ICP-CC408 | Installation Guide | 6.0
6.2.7

Turning Outputs On/Off

If an output is programmed for remote operation,
you can turn the remote output on or off using this
Master Code function or remotely using the Alarm
Link Software.
To use this Master Code function, you must program
one or more of the outputs with these Output Event
Types:
Output 1 = Output Event Type 2,8 (page 72)
Output 2 = Output Event Type 2,9 (page 72)
Output 3 = Output Event Type 2,10 (page 72)
To turn an output on from the remote codepad:
1. Enter your Master Code and press [5][AWAY].
Three beeps sound and the STAY and AWAY
indicators flash.
2. Enter the number of the output (1 to 3) and press
[AWAY].
Three beeps sound and the output turns on.
3. Repeat Step 2 to turn on another output.
4. Press [AWAY] to exit from this function.
Two beeps sound and the STAY and AWAY
indicators are extinguished.
Example
If Output 2 is programmed as 291000 in Locations
374 to 379, the Master Code holder can turn on this
output by entering:
[2 5 8 0 5][AWAY][2][AWAY][AWAY]
To turn off an output from the remote codepad:
1. Enter your Master Code and press [5][AWAY].
Three beeps sound and the STAY and AWAY
indicators flash.
2. Enter the number of the output (1 to 3) and press
[STAY].
Two beeps sound and the output turns off.
3. Repeat Step 2 to turn off another output.
4. Press [AWAY] button to exit from this function.
Two beeps sound and the STAY and AWAY
indicators are extinguished.
Example
If Output 2 is programmed as 291000 in Locations
374 to 379, the Master Code holder can turn off this
output by entering:
[2 5 8 0 5][AWAY][2][STAY][AWAY]
6.2.8

Setting the Date and Time

Use this function when the date and time must be
changed or if the system was powered down.
If the date and time is not set, the date and time fault
is shown only when the Auto Arming Time is
programmed in Locations 414 to 417 (refer to Section
17.12 Auto Arming Time on page 77), or when you
enter Fault Analysis Mode by holding down [5].
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
System Functions
To set the new date and time:
1. Enter your Master Code and press [6][AWAY].
Three beeps sound and the STAY and AWAY
indicators flash.
2. Enter the day, month, year, hour, and minute in
DD, MM, YY, HH, MM format (where DD is
the day of the month, MM is the month of the
year, YY is the year, HH is the hour of the day,
and MM minute of the day) and press [AWAY].
Use 24:00 hour format when programming the
hour of the day.
Two beeps sound and the STAY and AWAY
indicators are extinguished. If a long beep
sounds, there was an error when you entered the
date and time.
Example
To set the date and time for the 1st January 2004 at
10:30 PM, enter:
[2 5 8 0 6][AWAY][0 1 0 1 0 4 2 2 3 0][AWAY]
6.2.9

Walk Test Mode

Walk Test Mode allows you to test detection devices
to ensure they are functioning correctly. Before
activating Walk Test Mode, isolate any zones that are
not required for testing. Refer to Section 4.11 Isolating
Zones 4.11 Isolating Zones on page 23 for more
information.
To enter Walk Test Mode:
1. Enter your Master Code and press [7][AWAY].
Three beeps sound and the STAY and AWAY
indicators flash. The codepad beeps once per sec
when Walk Test Mode is active.
2. Unseal and seal the zones to be tested.
The codepad sounds one long beep and the horn
speaker sounds one short beep each time a zone
is sealed or unsealed.
3. Press [AWAY] to exit from this function.
Two beeps sound and the STAY and AWAY
indicators are extinguished. The system returns
to the disarmed state.
6.2.10

Event Memory Recall Mode

This function allows you to play back the last forty
system events that occurred. Event Memory Recall
Mode reports all alarms and each arming or
disarming of the system and helps with
troubleshooting system faults. The events are shown
using the codepad indicators.
To enter Event Memory Recall Mode:
Enter your Master Code and press [8][AWAY].
Three beeps sound. The events are played back by
the codepad indicators in reverse chronological
order.
EN | 38

Advertisement

Table of Contents
loading

Table of Contents