ICP-CC408 | Installation Guide | 16.0
The zone to which the fire/smoke detector is
connected should be programmed as:
ZONE TYPE = 13
ZONE PULSE COUNT = 3
ZONE PULSE COUNT TIME = 15
2,8
Remote Control 1
2,9
Remote Control 2
2,10
Remote Control 3
These outputs can be remotely activated (turned on
or off) by the following methods:
Remote codepad (refer to Section 6.2.7 Turning
Outputs On/Off on page 37 for more information).
Remotely through the Alarm Link Software
(refer to your Alarm Link Instruction Manual for
further information).
2,11
Radio Control Output 1
This output operates when the [DOOR] button on
the 4-channel hand-held transmitter is activated when
the system is armed or disarmed.
2,12
Radio Control Output 2
This output operates when the [AUX] button on the
4-channel hand-held transmitter is activated when the
system is armed or disarmed.
2,13
Radio Control Output 1 – Not in AWAY
Mode
This output operates when the [DOOR] button on
the 4-channel hand-held transmitter is activated when
the system is disarmed or armed in STAY Mode 1 or
STAY Mode 2. The output does not operate when
the system is armed in AWAY Mode.
2,14
Radio Control Output 2 – Not in AWAY
Mode
This output operates when the [AUX] button on the
4-channel hand-held transmitter is activated when the
system is disarmed or armed in STAY Mode 1 or
STAY Mode 2. The output does not operate when
the system is armed in AWAY Mode.
2,15
Communications Failure after Three
Unsuccessful Calls
This output operates after the communication dialer
makes three unsuccessful calls to the base station
receiver. The output is reset when all messages are
transmitted (that is, when the buffer is empty or when
all possible attempts are made).
3,0
Communications Failure
This output operates after the communication dialer
makes all possible attempts to reach the base station
receiver. The output is reset when the first Kiss-Off is
received. This output does not operate for domestic
formats.
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
Programmable Outputs
3,1
Dialer Disabled
This output operates when the Dialer reporting
functions allowed option (1) in Location 177 is not
selected (refer to Section 12.1 Dialer Options 1 on page
53). The output is reset when Option 1 is selected.
3,2
Dialer Active
This output operates when the communication dialer
is online. The output is reset when the
communication dialer releases the telephone line.
3,3
Ring Detect
This output operates when an incoming call is
detected by the control panel. The output is reset
when the ringing stops or when the call is answered.
3,5
Mimic Zone 1
3,6
Mimic Zone 2
3,7
Mimic Zone 3
3,8
Mimic Zone 4
3,9
Mimic Zone 5
3,10
Mimic Zone 6
3,11
Mimic Zone 7
3,12
Mimic Zone 8
These output types mimic the zone inputs. The
output operates when the zone is unsealed and is
reset when the zone is sealed. They operate
regardless of the selected zone type (for example, a
zone programmed as Not Used can still operate a
mimic output). This feature operates when the system
is armed or disarmed.
4,5
Global Chime
This output operates when any Chime zones are
activated. The output is reset when the zone is
resealed. Refer to Section 14.3.2 Zone Types on page 58
for more information.
4,6
Zone Not Sealed
This output operates when a Burglary Zone is
unsealed. Chime zones do not operate this output.
4,7
Zone Not Sealed after Exit Time
This output operates at the end of Exit Time if a
Burglary Zone is unsealed. The output is reset when
all zones are sealed or the system is disarmed. Chime
zones do not operate this output.
4,9
AC MAINS 60 Hz or 50 Hz
This output is activated when the AC MAINS supply
frequency is 60 Hz. The output is reset if the AC
MAINS supply returns to 50 Hz.
Output Event Types 4,10 through 6,1
below are available only to partitioned
ICP-CC408 Control Panels.
EN | 72