Bosch ICP-CC408 Installation Manual page 71

Table of Contents

Advertisement

ICP-CC408 | Installation Guide | 16.0
1,8
Codepad Medical Alarm
This output operates when a user activates a
Codepad Medical Alarm by pressing [7] and [9] at
the same time on the remote codepad. This output is
reset when a valid User Code is entered at the
remote codepad.
1,9
Codepad Fire Alarm
This output operates when a user activates a
Codepad Medical Alarm by pressing [4] and [6] at
the same time on the remote codepad. This output is
reset when a valid User Code is entered at the
remote codepad.
1,10
Codepad Panic Alarm
This output operates when a user activates a
Codepad Panic Alarm (audible or silent) by pressing
either [1] and [3] or [STAY] and [AWAY] at the
same time on the remote codepad. This output is
reset when a valid User Code is entered at the
remote codepad.
1,11
Codepad Duress Alarm
This output operates when a user activates a Duress
Alarm by adding a 9 to the end of the User Code
used to disarm the system. This output is reset the
next time the system is armed.
1,12
Codepad Tamper – Access Denied
This output operates when the wrong code is entered
more times than allowed. The number of incorrect
attempts allowed is programmed in Location 356
(refer to Section 15.19 System Status – Access Denied on
page 67). This output is reset when a valid User Code
is entered.
1,14
Horn Speaker (Output 1 Only)
This output operates only on Output 1. Use this
output for one or two 8 Ω horn speakers. Refer to
Section 17.9 Siren Run Time on page 77 and Section
17.10 Siren Sound Rate on page 77 to program the
speaker.
To enable monitoring of the horn speaker, select
Option 2 in Location 424 (refer to Section 18.1 System
Options 1 on page 78).
1,15
Sirens Running
This output operates for the duration of the Siren
Run Time programmed in Location 411 (refer to
Section 17.9 Siren Run Time on page 77). When the
sirens are activated, this output is reset when the
Siren Run Time expires. The relay output (Output 4)
is set by default for this operation.
2,0
Strobe Operating
This output operates when an alarm occurs and is
reset when a valid User Code is entered. The strobe
output (Output 3) is set by default for strobe
operation and is programmed to reset automatically
after 8 hours.
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
Programmable Outputs
2,1
Silent Alarm
This output operates when any zone programmed to
be silent activates. The output is reset when the Siren
Run Time expires, an audible alarm is activated, or a
valid User Code is entered.
2,2
Alarm When in STAY Mode
This output operates when an audible or silent alarm
zone is activated when the system is armed in STAY
Mode 1 or STAY Mode 2. The output is reset when
the system is disarmed.
2,3
Alarm When in AWAY Mode
This output operates when an audible or silent zone
alarm is activated when the system is armed in
AWAY Mode. The output is reset when the system is
disarmed.
2,4
Mimic System Fault
This output operates without any time delays when
any system fault occurs, including an AC MAINS
supply failure. The output is reset when the system
fault or the AC MAINS supply is restored.
2,5
Fire Alarm Resetting
This output operates when a 24-Hour Fire Zone is
activated. The output is reset when a valid User
Code is entered or when Siren Run Time expires.
2,6
Fire Alarm Latching
This output operates when a 24-Hour Fire Zone is
activated and is reset when the system is armed or
disarmed.
2,7
Fire Alarm Verification
This feature is used on some commercial fire control
panels to reduce false alarms from smoke detectors.
It is very similar to zone pulse count used in some
motion detectors. A fire zone is allotted a pulse count
of 3 pulses over a period of 3 min.
If the smoke detector trips, the voltage to the smoke
detector is disconnected for 15 sec and then
reapplied. No alarm is registered.
If the unit activates again within 3 min of the first
activation, no alarm is registered and the voltage to
the smoke detector is again disconnected for 15 sec
and then reapplied.
If a third activation is detected within 3 min of the
first activation, (three pulses in 3 min) a fire alarm is
registered. Power to the smoke detector is maintained
to facilitate unit identification through the detector
memory.
Connect this output to the negative side of any fire or
smoke detector. To configure an output for this
feature, use these settings.
EVENT TYPE = 2,7
POLARITY = 10
TIMEBASE = 2
MULTIPLIER = 15
EN | 71