| Table of contents Solution 4000 control panel 5.1.20 A-Link Plus Options Installer Code User Code Programming (User 1–32) User Code Programming (User 33–64) Day Alarm Zones EOL Resistor Value B228 EOL Resistor Value Zone Programming (Zone 1–16) Zone Programming (Zone 17–32) 5.10...
Solution 4000 control panel Table of contents | en 5.22.13 Kiss-Off Wait Time 5.22.14 Speaker Beep Volume 5.23 Options Programming 5.23.1 System Options 1 5.23.2 System Options 2 5.23.3 System Options 3 5.23.4 System Options 4 5.23.5 System Options 5 5.23.6...
| Safety Solution 4000 control panel Safety Use latest software Before operating the device for the first time, make sure that you install the latest applicable release of your software version. For consistent functionality, compatibility, performance, and security, regularly update the software throughout the operational life of the device.
Introduction | en Introduction Thank you for choosing Solution 4000 control panel for your installation. You will find this system extremely flexible, reliable, and easy to use. This quick installation guide is supplied with the system to provide users with enough basic information to wire, configure, and program the system.
Page 8
| Introduction Solution 4000 control panel Receiver WE800EV2 and B810 are mutually exclusive. Up to two B426-M/ B450-M can be used per system. 2024-09 | V01 | F.01U.418.606 Bosch Security Systems B.V. Quick installation guide...
Solution 4000 control panel Programming | en Programming The programming options of the system are stored in a non-volatile EPROM. This memory holds all information during a total power loss and can be changed as many times as required. The entire programming sequence consists of entering a location number and changing the data as required.
Page 10
| Programming Solution 4000 control panel AWAY Arm STAY1 Arm STAY2 Arm Installer Passcode Fault analysis Day alarm Event recall Arm/disarm seq. Inquire Cloud status Report monitor Modem call init. Command System Domestic phone Version display RF Zone Factory default...
Page 11
Solution 4000 control panel Programming | en Installer Passcode Zone config [267, 9934, 13252] Zone allocate [502, 10046] Zone Zone name [2536, 10794] Day alarm zone [265] STAY2 zone [381] EOL resistor [266, 389] Zone state report [392] Siren swing shutdown count...
| Programming Solution 4000 control panel 3.1.1 Programming Text When programming text via the Alphanumeric codepad, enter sensitive alphanumeric characters as the table below. Each numeric key represents a different group of characters. Pressing the same numeric key repeatedly will step you through the available characters assigned to the key.
Page 13
Solution 4000 control panel Programming | en Task Keystrokes Enter Installer’s Programming Mode [1234#] Exit from Installer’s Programming Mode [958#] without saving changes Exit from Installer’s Programming Mode with [960#] saving changes and panel reset Step to next Location Step back one Location...
| Programming Solution 4000 control panel Programming Option Bits Use option bits to program any combination of the four different options in one location by adding the options together. Programming a zero disables all four options. Example If at Location 0178 you only want options 1, 2, and 4, add the numbers together and the total is the number to be programmed.
Solution 4000 control panel Operating commands | en Operating commands The system supports programmable 1 - 4 - digit Installer code or User Code to execute the following operating commands. No identical User Codes are allowed. User Codes are not permitted to be the same as Installer codes.
Page 16
| Operating commands Solution 4000 control panel Master/User Command Function Description Access Code+[5][#] Turn Output On/Off Code+[6][#] Setting the Date and Time Code+[7][#] Walk Test Mode Code+[8][#] Event Memory Recall Mode Code+[9][#] Duress Disarm Code+[*] STAY 1 Arm / Disarm or STAY 2 Disarm...
Page 17
Solution 4000 control panel Operating commands | en Long Press Command Function Description Access Hold-down [7] 3sec Reset Latching Output (AUI) Hold-down [8] Change the Codepad Buzzer Tone and (AUI) Codepad Area Display Hold-down [9] 3sec Send Test Report (AUI)
| Operating commands Solution 4000 control panel Add/Delete RF Device (Wireless Zones) Notice! Set RF receiver as RADION Receiver B810 (Value 1 in Location 395), and set Zone Source of RF zones as RF (Location 754 to 769). Notice! Only zone number 1 to 16 displays through zone indicators on the ICON codepad.
Solution 4000 control panel Operating commands | en Add/Delete RF Repeater Notice! Set RF receiver as RADION Receiver B810. Add RF Repeater Enter the Installer Code, followed by [0] and the [#] key (for example, [12340#]). Enter the point ID of RADION Repeater (822 to 829) you want to add (822 = 1,823 = 2, etc.), followed by the [#] key.
| Operating commands Solution 4000 control panel Add Keyfob on RADION B810 Notice! Set RF receiver as RADION Receiver B810 (Value 1 in Location 395). Enter the Master Code, followed by [1] and the [#] key (for example, [25801#]).
Solution 4000 control panel Operating commands | en Set the Number of Days until the First Test Report Enter the Installer Code, followed by [1] and the [#] key. Enter the Number of Days (0 to 15) until the first Test Report is sent, followed by the [#] key.
| Operating commands Solution 4000 control panel Zone LED for Zone LED for Report Event Receiver 1/3 Receiver 2/4 Dialing Telephone Number / Network Connect Handshake Received Data Being Sent Kiss-Off Received None None Released Telephone Line / Idle Table 4.11: Report Monitor Mode Indications...
Page 23
Solution 4000 control panel Operating commands | en To further determine the type of fault condition, press the key that corresponds to the zone indicator displayed. For example, if Zone 1 displayed System Fault, press the [1] key to display which system fault occurred.
Page 24
| Operating commands Solution 4000 control panel Output 1 to 3 Fail - This fault registers when the system detects output 1 - 3 as warning device (Horn Speaker, Siren Running, Strobe) is disconnected or short. This fault clears once all outputs are reconnected.
Solution 4000 control panel Operating commands | en 9 Door and Power Supply Module Fail The power supply module fault registers when the B520 power supply module is disconnected or tampered, or the power supply module battery 1 or 2 is disconnected.
Solution 4000 control panel Programming Parameters | en Item Location Option Default New CSVIP User Name and 1300 - 1363 Password Conettix Anti-replay 1400 1 = Anti-replay for Receiver 1 Enable 2 = Anti-replay for Receiver 2 Enable 4 = Anti-replay for Receiver 3 Enable...
Page 28
| Programming Parameters Solution 4000 control panel Item Location Option Default New 4 = Domestic 5 = Conettix IP 6 = SIA Fast 7 = SIA Slow 8 = CSVIP 9 = Email Subscriber ID Number 1491 - 1496...
Solution 4000 control panel Programming Parameters | en Program Email with A-Link Plus Software Notice! For the network module B426, Panel Programming Enable shall be defaulted Yes in the Maintenance Page of the web-based configuration menus. Notice! When A- Link Plus is used to configure the network module, network module parameters will be replaced by parameters configured in A - Link Plus.
| Programming Parameters Solution 4000 control panel 5.1.16 Telephone Line Fail Options Item Location Option Default New Telephone Line Fail 0176 1 = Display FAULT Indicator when Options telephone line fails 2 = Sound alarm when system is armed...
Solution 4000 control panel Programming Parameters | en 5.1.20 A-Link Plus Options Item Location Option Default New A-Link Plus Options 0180 1 = Enable upload/download using A- Link 2 = Enable A-Link callback 4 = Terminate A-Link connection on alarm...
| Programming Parameters Solution 4000 control panel Day Alarm Zones Item Location Option Default New Day Alarm Zones 0265 1 = Zone 1 2 = Zone 2 4 = Zone 3 8 = Zone 4 EOL Resistor Value Item...
Page 37
Solution 4000 control panel Programming Parameters | en Item Location Default Item Location Default Reserved 0272 Reserved 0279 Zone Report Options 0273 Zone Report Options 0280 Zone #03 Zone #04 Zone Type 0281 Zone Type 0288 Zone Pulse Count 0282...
Page 38
| Programming Parameters Solution 4000 control panel Item Location Default Item Location Default Zone Options 1 0326 Zone Options 1 0333 Zone Options 2 0327 Zone Options 2 0334 Reserved 0328 Reserved 0335 Zone Report Options 0329 Zone Report Options...
Page 39
Solution 4000 control panel Programming Parameters | en Item Location Default Item Location Default Zone 5 Source 0758 Zone 6 Source 0759 Zone 7 Source 0760 Zone 8 Source 0761 Zone 9 Source 0762 Zone 10 Source 0763 Zone 11 Source...
| Programming Parameters Solution 4000 control panel Item Option Keyswitch Zone Options 0 = Latching arm and disarm in AWAY Mode 1 = Latching arm in AWAY Mode 2 = Latching disarm from AWAY Mode or STAY Mode 4 = Latching arm and disarm in STAY Mode 1...
Page 41
Solution 4000 control panel Programming Parameters | en Item Location Default Item Location Default Reserved 9953 Reserved 9960 Zone Report Options 9954 Zone Report Options 9961 Zone #21 Zone #22 Zone Type 9962 Zone Type 9969 Zone Pulse Count 9963...
Page 42
| Programming Parameters Solution 4000 control panel Item Location Default Item Location Default Zone Options 1 10007 Zone Options 1 10014 Zone Options 2 10008 Zone Options 2 10015 Reserved 10009 Reserved 10016 Zone Report Options 10010 Zone Report Options...
Solution 4000 control panel Programming Parameters | en 5.10 Door Associated Zone Programming (Zone 129–132) Item Location Default Item Location Default Zone #129 Zone #130 (Door 1 zone) (Door 2 zone) Zone Type 13252 Zone Type 13259 Zone Pulse Count...
| Programming Parameters Solution 4000 control panel Item Location Option Default New STAY Mode 2 0381 1 = Zone 1 4 = Zone 3 Automatically Bypass 2 = Zone 2 8 = Zone 4 Zones 0382 1 = Zone 5...
Solution 4000 control panel Programming Parameters | en Item Location Option Default New 1 = Australia 2 = New Zealand 3 = Customized DST Customize DST + 1 hour Month 0417 0 = No DST 1 to 12 = January to December...
| Programming Parameters Solution 4000 control panel 5.18.2 System Status Reporting Options Item Location Option Default New System Status 0427 0 = No report required Reporting Options 1 = Report to Receiver 1 2 = Report to Receiver 2...
Solution 4000 control panel Programming Parameters | en Item Location Default Item Location Default Polarity 0744 Polarity 0750 Time Base 0745 Time Base 0751 Time Base Multiplier 0746 Time Base Multiplier 0752 Time Base Multiplier 0747 Time Base Multiplier 0753...
| Programming Parameters Solution 4000 control panel 5.22.2 Entry Time 2 Item Location Option Default New Increments of 1 sec. (0 to 15 sec.) 0468 Increments of 16 sec. (0 to 240 sec.) 0469 5.22.3 Exit Time (AWAY/STAY Modes)
Solution 4000 control panel Programming Parameters | en 5.22.9 Siren Sound Rate Item Location Option Default New Siren Sound Rate 0480 0 = Slowest frequency 15 = Fastest frequency 5.22.10 Auto Arming Pre-Alert Time Item Location Option Default New Auto Arming Pre-Alert Time...
Solution 4000 control panel Programming Parameters | en Item Location Option Default New 0109 System-wide Tamper (choose either 0 or 1 or 2 or 3): (4 + 3) 0 = Tamper is ignored 1 = Silent Alarm for Tamper 2 = Audible Alarm for Tamper...
| Programming Parameters Solution 4000 control panel Item Location Option Default New 4 = Alarms activate sirens and strobe outputs in STAY Modes 1 and 2 8 = Zone tamper alarms to be silent 5.23.9 Partitioning Options 1 Item...
Solution 4000 control panel Programming Parameters | en Item Location Default Item Location Default Zone 3 Area 10048 Zone 4 Area 10049 Zone 5 Area 10050 Zone 6 Area 10051 Zone 7 Area 10052 Zone 8 Area 10053 Zone 9 Area...
| Programming Parameters Solution 4000 control panel Item Location Default New Item Location Default User Code 29 0562 User Code 30 0563 User Code 31 0564 User Code 32 0565 Option 0 = User code not assigned 2 = User code assigned to Area 2...
Solution 4000 control panel Programming Parameters | en 5.26 Codepad Assigned Door Item Location Option Default New Codepad 1 door 0522 0 = Door 1 1 = Door 2 Codepad 2 door 0523 2 = Door 3 Codepad 3 door...
Home Message blank 5.30.2 User Names In the A-Link Plus, select One Solution -> Solution 4000, then go to Access -> User Property, select the user and enter up to 12 case sensitive alphanumeric characters for the user name. Item...
Zone 31 Name Zone 32 Name 5.30.4 Area Names In the A-Link Plus, select One Solution -> Solution 4000, then go to Area -> Area 1 Name or Area 2 Name, enter up to 12 case sensitive alphanumeric characters. Item Item...
Solution 4000 control panel Programming Parameters | en 5.30.7 Doors In the A-Link Plus, select One Solution -> Solution 4000, then program the door access parameters: – Go to Access -> User Property, set the User Allocate and User Authority for the users who will operate the door functions.
| Appendices Solution 4000 control panel Appendices Connections for EOL Resistors Zone 1 Zone 1 Zone 1 Zone 1 Zone 9 (3K3 EOL) (6K8 EOL) Zone 9 TAMPER (6K8 EOL) TAMPER Zone 1 (3K3 EOL) Callout - Description 1 - Zone without resistor (Location 266 = 0 (No EOL), Location 266 = 12 (Normal open))
Solution 4000 control panel Appendices | en Callout --Description Callout --Description 4 - Zone 5-8 termination strip (for zone 5-8 11 - Bosch SDI2 Bus and zone 13-16) 5 - AUX power 12 - Relay contact select (Select output AUX...
Page 74
| Appendices Solution 4000 control panel 2024-09 | V01 | F.01U.418.606 Bosch Security Systems B.V. Quick installation guide...