7.2

Switch Setting

Set the output range, HOLD/CLEAR function, drive mode, and output mode used for each channel.
(1) Setting procedure
Open the "Switch Setting" window.
Project window
Item
Output range
Output Range
Setting
HOLD/CLEAR
*1
function
Drive Mode Setting
56
[Intelligent Function Module]
Description
Set the output range used in each channel.
Select whether to hold or clear the output analog
value (output offset value) in each channel when
the CPU module enters to the STOP status or
when an error occurs.
Set the drive mode of the D/A converter module.
Set "Offset/Gain Setting Mode" to configure the
offset/gain setting with the user range setting
being selected.
module name
[Switch Setting]
Setting value
• 4 to 20mA (default value)
• 0 to 20mA
• 1 to 5V
L60DA4
• 0 to 5V
• -10 to 10V
• User Range Setting
• 1 to 5V (default value)
• 0 to 5V
L60DAVL8
• -10 to 10V
• User Range Setting
• 4 to 20mA (default value)
L60DAIL8
• 0 to 20mA
• User Range Setting
• CLEAR (default value)
• HOLD
• Normal (D/A Converter Processing) Mode (default value)
• Offset-Gain Setting Mode