7.2

Parameter Settings for CC-Link

This section describes the settings for CC-Link.
The following two methods are available for the settings for CC-Link.

• Setting with the switch

• Setting using the engineering tool
7.2.1
Setting with the switch
Follow the procedures below to set CC-Link.
1.
Detecting the CC-Link remote stations
Execute the automatic CC-Link startup so that the bridge module detects the CC-Link remote station.
( Page 55, Section 7.2.1 (1))
2.
Saving the parameters
Save the information of the CC-Link remote station as parameters into the bridge module. Then restart
CC-Link. ( Page 57, Section 7.2.1 (2))
3.
Checking the status of communications
Execute a line test in CC-Link to check the communication status. ( Page 64, Section 7.2.3)
(1) Detecting the CC-Link remote stations
The automatic CC-Link startup enables the bridge module to recognize the CC-Link remote stations and start
CC-Link only by powering on the module.
After executing the automatic CC-Link startup, set the parameters with the slave station information saving. (
Page 57, Section 7.2.1 (2))
Master/local module
CC-Link IE Field Network
CC-Link IE Field Network slave stations
Station No.1
remote I/O station
CC-Link
Station No.2
Station No.3
remote I/O station
remote device station
remote I/O station
Connected stations
not connected
The number of connected stations: 64
Startup mode switch
The automatic CC-
Link startup can be
executed with the
startup mode switch
set to AUTO.
Bridge module
Station No.4
Station No.5
remote device station
remote I/O station
Station
Connected station
CHAPTER 7 VARIOUS SETTINGS
Station No.6
Station No.64
remote I/O station
Stations not connected
Default setting with the
automatic CC-Link startup
7
55