(4) I/O conversion characteristic of the L60DAVL8
10
5
1
0
-5
-10
No.
Output range setting
1)
1 to 5V
2)
0 to 5V
3)
-10 to 10V
User range setting
*1
Set the offset value and gain value in user range setting within the range satisfying the following two conditions.
• Setting range: -10 to 10V
• Gain value - offset value 2.6V
*2
Maximum resolution in the user range setting.
Use the value within the practical digital input range and practical analog output range of each output range. If a value out of
the range is used, the accuracy may not fall within the range of performance specifications. (Do not use the value in the
dotted line in the graph above.)
1)
3)
-16384
-16000
-8000
0
Digital value
Offset value
Gain value
1V
5V
0V
5V
0V
10V
*1
2)
8000
8191
16000
16383
Digital value
0 to 8000
-16000 to 16000
*1
-8000 to 8000
APPX
A
Resolution
500V
625V
625V
*2
320V
219