Mitsubishi Electric MELSEC L Series User Manual page 114

Digital-analog converter module
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

[Precaution]
The setting also can be configured through "D/A conversion enable/disable setting" in "Parameter" of GX
Works2.
1.
Start "Parameter"
Project window
2.
Set "D/A conversion enable/disable setting" to "0: Enable".
When the setting is configured by the above procedure, an error occurs if the setting content is activated
by resetting the CPU module or by turning off and on the power. The error code (33) is stored in Latest
error code (Un\G19), Error flag (XF) turns on, and the ERR.LED turns on. This error occurs because the
wave pattern data points setting is set to 0 (default value) for the channel where D/A conversion enable is
set. To clear this error, register wave data and parameters for the wave output function, then turn OFF 
ON  OFF Operating condition setting request (Y9) as in the procedure described in Page 113, Section
8.8.2 (1).
112
[Intelligent Function Module]
[Parameter]
module name