5. DIP switch setting

5.1 DIP switch functions
Located on the FTC printed circuit board are 7 sets of small white switches known
as DIP switches. The DIP switch number is printed on the circuit board next to
the relevant switches. The word ON is printed on the circuit board and on the DIP
switch block itself. To move the switch, you will need to use a pin or the corner of
a thin metal ruler or similar.
DIP switch settings are listed below in Table 5.1.1.
Only an authorised installer can change DIP switch setting under one's own re-
sponsibility according to the installation condition.
Make sure to turn off both indoor unit and outdoor unit power supplies before
changing the switch settings.
For multiple outdoor units control with FTC (sub), see section 10.3.2.
DIP switch
Function
SW1 SW1-1 Boiler
SW1-2 Heat pump maximum outlet water temperature
SW1-3 DHW tank
SW1-4 Immersion heater
SW1-5 Booster heater
SW1-6 Booster heater function
SW1-7 Outdoor unit type
SW1-8 Wireless remote controller
SW2
SW2-1 Room thermostat1 input (IN1) logic change
SW2-2 Flow switch1 input (IN2) logic change
SW2-3 Booster heater capacity restriction
SW2-4 Cooling mode function
Automatic switch to backup heat source opera-
SW2-5
tion (When outdoor unit stops by error)
SW2-6 Mixing tank
SW2-7 2-zone temperature control
SW2-8 Flow sensor
SW3
SW3-1 Room thermostat 2 input (IN6) logic change
SW3-2 Flow switch 2 and 3 input logic change
SW3-3
SW3-4 Electric energy meter
SW3-5 Heating mode function *3
SW3-6 2-zone valve ON/OFF control
SW3-7
SW3-8 Heat meter
SW4 SW4-1 Multiple outdoor unit control
SW4-2 Position of multiple outdoor unit control *7
SW4-3
SW4-4 Indoor unit only operation (during installation work) *4
SW4-5 Emergency mode (Heater only operation)
SW4-6 Emergency mode (Boiler operation)
SW5 SW5-1
SW5-2 Advanced Auto Adaptation
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8
SW6
SW6-1
SW6-2
SW6-3 Pressure sensor
SW6-4 Analog output signal (0-10V)
SW6-5
SW6-6
SW6-7
SW6-8
WITHOUT Boiler
55ºC
WITHOUT DHW tank
WITHOUT Immersion heater
WITHOUT Booster heater
For heating only
Split type
WITHOUT Wireless remote control-
ler
Zone 1 operation stop at thermostat
short
Failure detection at short
Inactive
Inactive
Inactive
WITHOUT Mixing tank
Inactive
WITHOUT Flow sensor
Zone 2 operation stop at thermostat
short
Failure detection at short
WITHOUT Electric energy meter
Inactive
Inactive
WITHOUT Heat meter
Inactive
Sub
Inactive
Normal
Normal
Inactive
Inactive
Inactive
OFF
ON
WITH Boiler
60ºC
WITH DHW tank
WITH Immersion heater
WITH Booster heater
For heating and DHW
Packaged type
WITH Wireless remote controller
Zone 1 operation stop at thermostat
open
Failure detection at open
Active
Active
Active *2
WITH Mixing tank
Active *6
WITH Flow sensor
Zone 2 operation stop at thermostat
open
Failure detection at open
WITH Electric energy meter
Active
Active
WITH Heat meter
Active
Main
Active
Emergency mode (Heater only opera-
tion)
Emergency mode (Boiler opera-
tion)
Active
Active
Active
<Fig. 5.1.1>
Default settings:
Indoor unit model
OFF
ON *1
OFF: PAC-IF081B-E
ON : PAC-IF082/083B-E
OFF: PAC-IF081B-E
ON : PAC-IF082/083B-E
OFF
OFF
OFF: PAC-IF081B-E
ON : PAC-IF082/083B-E
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF *5
OFF *5
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF: PAC-IF081/082B-E
ON: PAC-IF083B-E
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SW4
SW6
SW5
SW3
SW2
SW1
SW7
en
26