8.8.3

Points for the use of the wave output function

(1) When turning on or off CH Output enable/disable flag (Y1 to Y8) during the
wave output
When CH Output enable/disable flag (Y1 to Y8) is turned off during the wave output, the analog output value
becomes the offset value though the wave output is continued. The wave output continues to be updated while
CH Output enable/disable flag (Y1 to Y8) is off. When CH Output enable/disable flag (Y1 to Y8) is turned on,
the analog output is resumed.
Wave data
118
CPU module status
D/A conversion enable/disable setting
(Un\G0)
CH
Output enable/disable flag
(Y1 to Y8)
CH
Wave output start/stop request
(Un\G1000 to Un\G1007)
CH
Wave output status monitor
(Un\G1100 to Un\G1107)
Output set in CH
Output setting
during wave output stop
(Un\G1008 to Un\G1015)
Offset value
RUN
D/A conversion enable (0)
OFF
ON
Wave output stop
request (0)
Wave output stop (0)
Analog output
OFF
ON
Wave output start request (1)
Wave output
Wave output (1)
stop (0)