Mitsubishi Electric MELSEC L Series User Manual page 146

Digital-analog converter module
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

• To apply the offset/gain values of one module to the other modules:
Sets values in Pass data classification setting (Un\G200).
(This setting is not required for the L60DAVL8 and L60DAIL8.)
Turns off, then on, and off again Operating condition
setting request (Y9).
Records the values stored in the following buffer memory areas.
• Pass data classification setting (Un\G200) (only L60DA4)
• Un\G202 to Un\G233
Write the recorded data in the following buffer memory areas.
• Pass data classification setting (Un\G200) (only L60DA4)
• Un\G202 to Un\G233
Turns off and then on User range writing request (YA).
Checks that Offset/gain setting mode flag (XA) is on.
Turns on and then off User range writing request (YA).
Turns off, then on, and off again Operating condition
setting request (Y9).
Checks that the replaced D/A converter module operates
with the restored offset/gain values.
When the data is written to the following buffer memory address in the source D/A converter module and User range writing
request (YA) is turned from OFF to ON, the D/A conversion is stopped.
● For the L60DA4: Pass data classification setting (Un\G200), CH1 Industrial shipment settings offset value (Un\G202) to
CH4 User range settings gain value (Un\G217)
● For the L60DAVL8 and L60DAIL8: CH1 Industrial shipment settings offset value (Un\G202) to CH8 User range settings
gain value (Un\G233)
Turn OFF  ON  OFF Operating condition setting request (Y9) to restart the D/A conversion.
144
Start
End
For the source D/A converter module
For the destination D/A converter module

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l60da4Melsec l60davl8Melsec l60dail8

Table of Contents