(3) Mode transitions
The following shows the transition condition of each mode.
Wave output mode
No.
Set "Drive Mode Setting" to "Normal (D/A Converter Processing) Mode" and set "Output mode setting" to "Normal Output Mode"
1)
in "Switch Setting" of GX Works2.
2)
Set "Drive Mode Setting" to "Offset-Gain Setting Mode" in "Switch Setting" of GX Works2.
Perform the mode transition by either of the following methods.
Method 1
3)
Method 2
Perform the mode transition by either of the following methods.
Method 1
4)
Method 2
Set "Drive Mode Setting" to "Normal (D/A Converter Processing) Mode" and set "Output mode setting" to "Wave Output Mode" in
5)
"Switch Setting" of GX Works2.
*1
The wave output mode is independent from other mode. After the start in the wave output mode, the transition to other
mode is not available. Also, after the start in other mode, the transition to the wave output mode is not available.
68
At the power-on or at the
reset of the CPU module
5)
*1
Normal output mode
Execute the G(P).OFFGAN (argument
Set the following values in Mode switching setting (Un\G158, Un\G159) and turn OFF ON OFF Operating
condition setting request (Y9).
• Un\G158: 0964H
• Un\G159: 4144H
Execute the G(P).OFFGAN (argument
Set the following values in Mode switching setting (Un\G158, Un\G159) and turn OFF ON OFF Operating
condition setting request (Y9).
• Un\G158: 4144H
• Un\G159: 0964H
1)
4)
3)
Transition condition
S
: 0: Switch to the normal output mode).
: 1: Switch to the offset/gain setting mode).
S
2)
Offset/gain
setting mode