(13)CH1 Scaling lower limit value (Un\G54) to CH8 Scaling upper limit value
(Un\G69)
Common
Set the scale conversion range for each channel.
For details on the scaling function, refer to the following.
• Scaling Function (
(a) Setting range
• Setting range: -32000 to 32000
• In the channel where a value out of the above setting range is set, an error occurs. The error code (90) is
stored in Latest error code (Un\G19), Error flag (XF) turns on, and the ERR. LED turns on.
• The value to be set must satisfy the condition of Scaling upper limit value > Scaling lower limit value. In the
channel where a value does not satisfy the condition, an error occurs. The error code (91) is stored in
Latest error code (Un\G19), and Error flag (XF) and the ERR.LED turn on.
• When Scaling enable/disable setting (Un\G53) is set to Disable (1), the settings for CH1 Scaling lower limit
value (Un\G54) to CH8 Scaling upper limit value (Un\G69) are ignored.
(b) Enabling the setting
Turn OFF  ON  OFF Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 0.
Because 0 is set as the default value, change the setting value for the scaling function.
196
Page 77, Section 8.6)