(3) Setting procedure
1.
Set "D/A conversion enable/disable setting" to "0: Enable".
Project window
2.
Set "Scaling enable/disable setting" to "0: Enable".
3.
Set values for "Scaling upper limit value" and "Scaling lower limit value".
Scaling upper limit value
Scaling lower limit value
● Your scaling settings must meet the following condition:
Scaling upper limit value > Scaling lower limit value
● In the channel where "Scaling enable/disable setting" is set to "0: Enable" in the wave output mode, an error occurs. The
error code (21) is stored in Latest error code (Un\G19), Error flag (XF) turns on, and the ERR.LED turns on.
● Even if the input range of the digital value is extended, the resolution does not become higher than that provided when
the scaling function is not used.
78
[Intelligent Function Module]
Item
module name
[Parameter]
Setting range
-32000 to 32000