(43)Wave data registry area (Un\G5000 to Un\G54999)
This area registers the wave data for analog output in the wave output mode.
This area can be set only in the wave output mode.
For details on the wave output function, refer to the following.
• Wave Output Function (
(a) Setting range
• The setting range depends on the set output range. Follow the setting range below.
Module
L60DA4
L60DAVL8, L60DAIL8
• In the channel where the wave data with a value out of the above setting range is output, an error occurs.
The error code (60) is stored in Latest error code (Un\G19), Error flag (XF) turns on, and the ERR.LED
turns on. The wave output continues. However, while the value out of the setting range is set, the
maximum or minimum value of the output range is output in analog.
Page 86, Section 8.8)
Output range
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
Common
Settable range
0 to 20479 (practical range: 0 to 20000)
-20480 to 20479 (practical range: -20000 to 20000)
0 to 8191 (practical range: 0 to 8000)
-16384 to 16383 (practical range: -16000 to 16000)