Details of buffer memory addresses

The following describes the details of the buffer memory addresses of the A/D converter module.
This chapter describes buffer memory addresses for CH1.
Latest error code
The latest error code detected in the A/D converter module is stored. For details, refer to the following.
Page 80 List of Error Codes
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Latest error code
■Clearing an error
Turn on and off 'Error clear request' (YF) or 'Operating condition setting request' (Y9). However, when 'Operating condition
setting request' (Y9) is turned on and off, the A/D conversion is reset and the processing is started from the beginning.
Latest address of error history
Among Error history  (Un\G3600 to Un\G3759), a buffer memory address which stores the latest error code is stored.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Latest address of error history
Latest alarm code
The latest alarm code detected in the A/D converter module is stored. For details, refer to the following.
Page 82 List of Alarm Codes
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Latest alarm code
■Clearing an alarm
Turn on and off 'Error clear request' (YF) or 'Operating condition setting request' (Y9). However, when 'Operating condition
setting request' (Y9) is turned on and off, the A/D conversion is reset and the processing is started from the beginning.
APPX
104
Appendix 3 Buffer Memory Areas
CH1
CH2
CH3
0
CH1
CH2
CH3
1
CH1
CH2
CH3
2
CH4
CH5
CH6
CH4
CH5
CH6
CH4
CH5
CH6
CH7
CH8
CH7
CH8
CH7
CH8