Customizing Parameter Lists

3.9. Customizing
Parameter Lists
64
Custom parameter lists can be made to mask off parameters from view,
depending on user access password level.
The OEM password level provides read and write access to all applicable
keypad operator parameters. A custom parameter list applies to all lower
password levels, although whether a parameter is viewable or has write access
also depends on each password level which has precedence over the custom
parameter list. Minimum password access levels for parameters are listed in
Section 8.1.
To create a custom parameter list, the syntax of the list to be created in a text
files is:
XXXX Y
XXXX = Hex Address of keypad operator parameter
Y =
1 -> ON (viewable),
0 -> OFF
Keypad operator parameter hex addresses are listed in Section 8.1.
Only parameter addresses listed as ON will be made available from the custom
parameter list.
A parameter address not listed is set as OFF.
Any information listed past Y is ignored.
Example:
LS01 Leveling Speed
Hex Address = 0881h
Password Level = Basic
LS02 High Speed
Hex Address = 0882h
Password Level = Basic
LC41 System Inertia
Hex Address = 0BA9h
Password Level = Adjuster
The list to be created:
0881 1
0882 0
0BA9 1
LC41 will be accessible regardless in the OEM password level.