KEB COMBIVERT F5 Operation Manual page 105

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Error/Message Alt.
(NUM)
no Error Low
nEOL2
Speed Over-
(20)
load
no Error Motor
nEdOH
Overheat
(11)
no Error Over-
nEOL
load
(17)
Power Unit Not
no_PU
Ready
(13)
Serial Com-
(166)
mand Speed
Error
/
Description
No more over-
load.
Over temperature
reset possible
No more over-
load.
Control card is
powered up, but
the power stage
is not, so conse-
quently it is not
seen by control
card.
Serial speed
command not
present at the be-
ginning of a run
Cause/Solution/Troubleshoot
Low speed overload has cleared and can be reset.
Motor overheat sensor reset and Error Motor Overheat
can be reset.
Overload counter has reached 0%, allowing motor to
cool and the error overload error may be reset.
The Power Unit Not Ready message may occur due to
the following conditions:
Control card powered up by external power supply, but
drive is not powered up by line. Since the drive is not
being powered by the line, the power stage cannot be
identified.
Connection issue between control card and power
stage.
For inverter housing sizes G, H, R, U, remove then
reconnect the ribbon cable connecting the control
card to the power stage at the control card connec-
tion.
For inverter housing sizes D, E, remove the control
card then re-seat, ensuring pin connections.
Switching power supply.
If reseating the ribbon cable does not resolve the
issue, then there may be a failure of the switching
power supply and the drive would need to be re-
placed or inspected and repaired by KEB.
When US04 = Serial Speed DIN66019 Service 49 (4),
Serial Speed DIN66019 Service 50 (5), the speed com-
mand must be received within t=2.5(LT01+LT03) sec. at
beginning of run. Not active on inspection run.Refer to
additional information at end of section
Drive Faults
105