Fault Data Logging - KEB COMBIVERT F5 Operation Manual

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Programming Menu
3.7.2. Fault Data
Logging
62
The fault data logging function can be used to capture a scope trace of up to
four parameters in high resolution before and after a drive fault is triggered.
The scope file is then saved to flash memory on the keypad operator and the
file can be transferred from the keypad operator via FTP and be imported
within Combivis 6 to evaluate the scope trace.
The function is available under Prog > File > Fault Logging Menu.
Parameter Selection
Up to four parameters from the Diagnostics Parameters and/or Field Bus
Configuration parameters can be selected for the scope trace. For each scope
channel, select the channel number 1 - 4, then select either Diagnostics
Parameters or Field Bus Configuration, then scroll through the corresponding
parameter list to select the parameter for the corresponding channel.
Function Enabled/Disabled
Select whether the logging function is active.
Base Block Checking
The Base Block status indicates the output transistors have been safely shut
off and are being blocked from further operation. It is not an error, but will
appear before an error. Another typical occurence would be if the drive enable
is dropped while current is being output.
When Base Block Checking is off the scope is triggered only by a drive fault.
When active, the scope trace will be triggered additionally by the base block
status.
Sample Time
Select the sample time of the scope trace in 5ms resolution.
Trigger Value
Percentage of the scope trace that is recorded before the trigger occurs with
the remainder of the trace after the trigger.
Last Fault Code
Indicates the last fault code. Refer to Section 6.16 Diagnostics Parameters
DG02 for text description of numerical fault code.