4.4.4 AUTO STOP SEQUENCE

a)
When remote start input is invalid, "Stop Delay" time is initiated;
b)
Once this "Stop Delay" has expired, the "High-speed Cooling Delay" is initiated;
c)
When "Stop Idle Delay" (if configured) starts, idle speed relay is energized and outputs;
d)
When "ETS Solenoid Hold" begins, ETS relay is energized and fuel relay is de-energized;
e)
When controller enters "Wait for Stop" time, it will judge whether genset has stopped
completely;
f)
After complete stop, controller will enter standby status; if genset cannot stop controller, it will
issue alarm (LCD displays
NOTE 1: Press stop key in auto start status, genset will stop and enter into stop mode simultaneously.
NOTE 2: In the process of crank rest time, when fuel output is disconnected and crank rest countdown is
less than 7s, preheat and ETS stop output; after crank rest time, ETS stop output is disconnected and fuel
outputs; preheat output is stopped before crank.

4.4.5 MANUAL START/STOP OPERATION

Manual Start: press
SEQUENCE). If water temperature high and abnormal voltage occur during the running process,
controller shall protect it to stop quickly.
Manual Stop: press
STOP SEQUENCE).
MGC300 Series Genset Controller User Manual
).
to start genset (Please refer to start procedure b~g of AUTO START
to stop the running genset (Please refer to stop procedure b~f of AUTO
Page 12 of 26