Landis+Gyr E470 Series User Manual page 67

Hide thumbs Also See for E470 Series:
Table of Contents

Advertisement

Configuration
Configuration
item
Billing
The date-time of the first billing
Calendar
calendar snapshot and the
periodicity of following ones after
that (where periodicity can be
1=daily; 2=weekly and 3=monthly)
Load Limit
The length of time in seconds which
Period
the Active Power Import needs to
continuously exceed the Load Limit
Power Threshold before a load
limiting event is deemed to have
occurred
Load Limit
the Active Power threshold in kW
Power
above which the measurement of a
Threshold
load Limit Period is commenced
Load Limit
The length of time in seconds after
Restoration
the Supply has been Armed
Period
following a Load Limiting Event
before the supply is Enabled by the
meter
Load Limit
The setting which controls the state
Supply State
of the Supply in the case of load
limiting occurring, being Disabled or
unchanged
Alerts
Settings to control whether to
Configuration
generate and send an alert when
Settings
certain events occur in the meter.
NOTE: See separate Events and
Alerts section.
Average RMS
The average RMS voltage above
Over Voltage
which an over voltage condition is
Threshold
reported.
Average RMS
The average RMS voltage below
Under Voltage
which an under-voltage condition is
Threshold
reported.
Average RMS
The length of time in seconds over
Voltage
which the RMS voltage is averaged
Measurement
Period
RMS Extreme
The duration in seconds used to
Over Voltage
measure an extreme over voltage
Measurement
condition.
Period
D000058620 en a – E470 Series 3 SMETS2 100 mm – ZCX310 – User Manual and Functional Description
Issue 1.2
Description
Billing Calendar Settings
Load Limit Settings
Alert Settings
Network Settings
Default
Unit / Type
configuration
midnight on
"Start
first day of
date Time/
each month
Periodicity
(1=daily,2=weekly,
3=monthly)
30
seconds
1000
kW
31536000
Seconds
unchanged
disabled/
unchanged
By default, all
Alerts
mandatory
Configuration
alerts
Settings
designated by
GBCS to be
"always on"
are enabled,
all other alerts
switched off.
258
Volts
212
Volts
1800
Seconds
180
Seconds
67/143
Remotely
configurable
via DCC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
© Landis+Gyr